What steps will reproduce the problem?
1.ReadHoldingRegisters(1, 1, 1);
What is the expected output? What do you see instead?
The PDU should contain 0x00, 0x00 for the starting address. Instead, the PDU
contains 0x00, 0x01.
What version of the product are you using? On what operating system?
Version 1.11.0
Please provide any additional information below.
Here is an excerpt from the Modbus Application Protocol:
"The MODBUS application protocol defines precisely PDU addressing rules.
In a MODBUS PDU each data is addressed from 0 to 65535.
It also defines clearly a MODBUS data model composed of 4 blocks that comprises
several elements numbered from 1 to n.
In the MODBUS data Model each element within a data block is numbered from 1 to
n."
And again:
"The previous figure shows that a MODBUS data numbered X is addressed in the
MODBUS PDU X-1."
So as you can see, the address transmitted in the PDU should be 1 less than the
address passed to the methods.