Industrial Water Management — Web SCADA & HMI

A custom browser-based SCADA/HMI for an industrial water-management testbed. The project brings together different controller and edge technologies behind one web monitoring interface.

The current implementation demonstrates five zone integrations:

  • Zone 01 — Water storage tank process: Python process simulator exposed over Modbus TCP and polled by the Node.js driver.
  • Zone 02 — Rockwell Micro850: EtherNet/IP communication using a Node.js driver based on st-ethernet-ip.
  • Zone 03 — CODESYS: OPC UA communication with a CODESYS Control Win runtime.
  • Zone 04 — IoT Edge: ESP8266 telemetry and bidirectional mode commands over MQTT.
  • Zone 05 — BACnet/IP: an independent irrigation-device simulator accessed by a dedicated Node.js BACnet client driver.

The web application uses HTML, CSS and vanilla JavaScript on the frontend, Node.js and Express on the backend, and PostgreSQL for equipment, tag configuration and historical readings.

This is an engineering testbed. It is intended to explore controller integration, protocol handling, data acquisition, operator interaction and IT/OT architecture. It is not presented as a production-ready or safety-certified control system.

Project architecture

flowchart TB
  subgraph FIELD["Field and control layer"]
    Z1["Zone 01<br/>Python water-process simulator"]
    Z2["Zone 02<br/>Rockwell Micro850"]
    Z3["Zone 03<br/>CODESYS Control Win"]
    Z4["Zone 04<br/>ESP8266 soil node"]
    Z5["Zone 05<br/>BACnet/IP device simulator"]
  end

  subgraph COMM["Communication layer"]
    MOD["Modbus TCP"]
    EIP["EtherNet/IP"]
    OPC["OPC UA"]
    MQTT["MQTT / Mosquitto"]
    BAC["BACnet/IP over UDP"]
  end

  subgraph APP["Custom Web SCADA"]
    BE["Node.js / Express"]
    FE["Browser HMI<br/>HTML / CSS / JavaScript"]
    DB[("PostgreSQL")]
  end

  Z1 <-->|"Modbus TCP"| MOD
  Z2 <-->|"EtherNet/IP"| EIP
  Z3 <-->|"OPC UA"| OPC
  Z4 <-->|"MQTT telemetry, status and commands"| MQTT
  Z5 <-->|"BACnet/IP"| BAC
  MOD <--> BE
  EIP <--> BE
  OPC <--> BE
  MQTT <--> BE
  BAC <--> BE
  BE <--> FE
  BE <--> DB
Loading

The backend acts as the integration layer between the controller-specific protocols and the browser HMI. The browser does not communicate directly with the PLCs.

Zone implementation and status

Zone Technology Integration Current scope
Zone 01 Python water-process simulator Modbus TCP Tank filling process, pump/valve model, live process values and whitelisted operator commands
Zone 02 Rockwell Micro850 EtherNet/IP Live tag polling and whitelisted Boolean commands through the Node.js driver
Zone 03 CODESYS Control Win OPC UA Live tag browsing and polling, operator commands and PLC-side process logic
Zone 04 ESP8266 MQTT Soil-moisture telemetry, device status, AUTO/MANUAL commands and acknowledgements
Zone 05 Simulated BACnet/IP device BACnet/IP over UDP Analog and binary process values, commandable Binary Outputs and process simulation
SCADA Custom Web HMI REST API Unified monitoring, zone cards, operator controls and communication status

The project also contains local process simulations. In particular, Zone 04 moisture telemetry is received from the ESP8266, while its valve command and flow indication remain simulated. The ESP8266 firmware's onboard LED indicates the selected firmware mode; it is not physical valve feedback.

Technology stack

Layer Technologies
Frontend HTML5, CSS3, vanilla JavaScript
Backend Node.js, Express
Database PostgreSQL
Zone 01 protocol Modbus TCP
Zone 02 protocol EtherNet/IP
Zone 03 protocol OPC UA
Zone 04 protocol MQTT
Zone 05 protocol BACnet/IP
MQTT broker Mosquitto
Edge device ESP8266 / Wemos D1
PLC environments Rockwell CCW / Micro800 and CODESYS

Key capabilities

  • Multi-brand integration through separate protocol-specific backend drivers.
  • Zone 01 Modbus TCP polling, tank/pump process simulation and explicit operator STOP-latch / RE-ENABLE semantics.
  • Zone 02 Micro850 polling and controlled Boolean writes.
  • Zone 03 OPC UA tag discovery from the CODESYS GVL_SCADA variable group.
  • Zone 03 command whitelist, pulse handling for edge-triggered commands and server-side interlock messages.
  • Zone 04 MQTT telemetry ingestion directly by the Node.js backend.
  • MQTT device status and command-result acknowledgement handling.
  • UDP broker discovery for the Zone 04 ESP8266 on a shared IPv4 subnet.
  • Shared PostgreSQL historian persistence for selected observations from Zones 01–05.
  • Live data freshness handling, including GOOD and UNCERTAIN quality states.
  • REST endpoints that separate the browser HMI from industrial protocol details.
  • Zone 05 BACnet/IP polling, normalized observations and whitelisted AUTO/MANUAL/START/STOP/FAULT_RESET commands.

Zone 02 — Rockwell Micro850

The Node.js driver is located at server/drivers/micro800/zone02.js.

  • Uses the st-ethernet-ip library.
  • Connects to the Micro850 using the configured PLC IP address.
  • Polls configured Zone 02 tags at a one-second interval.
  • Retries the connection after communication failure.
  • Serializes PLC requests to avoid overlapping read and write operations.
  • Uses a command whitelist. Start, Stop and Fault Reset are momentary pulse commands; Auto and Simulation Enable are level commands.
  • Reads the permissive before accepting a Start command.

Default PLC address: 192.168.203.1. Set ZONE02_PLC_IP to override it.

Zone 03 — CODESYS and OPC UA

The backend connects to CODESYS Control Win through OPC UA at:

opc.tcp://127.0.0.1:4840

The OPC UA client browses the GVL_SCADA variable group and polls discovered variables every second. Zone 03 commands are restricted to a whitelist:

HMI command PLC variable Handling
Start Z03_START 300 ms pulse
Stop Z03_STOP 300 ms pulse
Fault Reset Z03_FAULT_RESET 300 ms pulse
Auto Z03_AUTO Held TRUE
Manual Z03_AUTO Held FALSE

The PLC remains responsible for process logic. The API mirrors relevant interlocks to return clear operator feedback.

Zone 04 — MQTT and IoT Edge

The Zone 04 data path in the current SCADA implementation is:

ESP8266 soil node
      |
      | MQTT telemetry
      v
Mosquitto broker
      |
      v
Node.js MQTT client (server/mqtt.js)
      |
      +----> Live Zone 04 state / REST API
      |
      +----> PostgreSQL tag_values historian

The ESP8266 publishes a moisture payload every 15 seconds to:

  • Telemetry: zone4/soil01/data
  • Device status: zone4/soil01/status
  • Mode command: zone4/soil01/command
  • Command result: zone4/soil01/command_result

The Node.js service validates incoming moisture values (0–100), updates the live value and asynchronously stores valid readings against the Z04_MOISTURE tag in PostgreSQL.

Historian quality records the validity at acquisition time. The live value can become UNCERTAIN when it exceeds the configured freshness threshold. The default threshold is 300 seconds and can be changed with ZONE4_STALE_SECONDS.

The HMI's AUTO/MANUAL mode changes are sent to the ESP8266 and require a command acknowledgement. START, STOP and RESET operate on the local Zone 04 process simulation; they do not actuate a physical valve.

MQTT broker discovery

The SCADA backend listens for UDP discovery requests on port 1884 and advertises the MQTT broker's IPv4 address and TCP port (default 1883). The ESP8266 broadcasts after repeated MQTT connection failures and stores a discovered broker address in LittleFS.

Discovery is limited to a shared broadcast-enabled IPv4 subnet. It does not cross routers or VLAN boundaries.

Zone 05 — BACnet/IP

Zone 05 uses an independently runnable BACnet/IP device simulator in Radfar/bacnet-device-simulator. The SCADA backend acts as the BACnet client; the simulator does not depend on the SCADA database or HMI.

The driver is server/drivers/bacnet/zone05.js. It polls four Analog Inputs, two Binary Inputs and the AUTO-mode Binary Output, then exposes normalized observations through the SCADA API. Operator commands are restricted to AUTO, MANUAL, START, STOP and FAULT_RESET. START, STOP and FAULT_RESET are momentary requests: the driver writes ACTIVE at priority 8, then relinquishes the command slot so the request can be issued again. AUTO/MANUAL is a held command.

At startup, the driver sends BACnet Who-Is discovery requests to the local IPv4 subnet broadcast addresses (and optionally to a configured unicast IP), filtered for device instance 10005. It learns the simulator's current IP and UDP source port from its I-Am response, then starts polling. Discovery retries automatically if the device is not found. Because the simulator uses UDP 47809, the driver explicitly directs Who-Is broadcasts to UDP 47809 rather than the BACnet default UDP 47808. Discovery is intended for devices on the same broadcast-enabled subnet; routed networks require BBMD/Foreign Device Registration or a configured unicast target.

The simulator exposes:

BACnet object Instances Purpose
Analog Input 1–4 Moisture, flow, valve position and tank level
Binary Input 1–2 Pump running and fault status
Binary Output 1–4 AUTO/MANUAL, START, STOP and FAULT RESET

See the simulator README and its learning journal for the object map, process model, YABE commissioning notes and validation history.

Shared PostgreSQL historian

The five zone integrations use a common historian writer and the existing PostgreSQL tags and tag_values tables. Protocol-specific drivers retain responsibility for acquisition; the shared service applies a consistent persistence contract and writes accepted observations to the same history table.

Historian coverage

Zone Source Persisted tags Acquisition / storage behavior
Zone 01 Python simulator / Modbus TCP P01_FREQUENCY, P01_SPEED, P01_FLOW, P01_RUN_FEEDBACK, P01_FAULT, Z01_OPERATOR_STOP_LATCHED, T01_LEVEL, V01_POSITION Polled; sampled at the configured historian interval
Zone 02 Micro850 / EtherNet/IP All 17 tags in the driver registry Polled; sampled at the configured historian interval
Zone 03 CODESYS / OPC UA Z03_MOISTURE, Z03_FLOW, Z03_VALVE, Z03_FAULT, Z03_AUTO Selected allow-listed variables; sampled at the configured interval
Zone 04 ESP8266 / MQTT Z04_MOISTURE Event-driven; a validated moisture message is stored when received
Zone 05 BACnet/IP Seven observations exposed by the BACnet driver Polled; sampled at the configured historian interval

The default sampling interval for Zones 01, 02, 03 and 05 is five seconds. Set HISTORIAN_SAMPLE_INTERVAL_MS to change it. Zone 04 remains event-driven and is not throttled by that interval.

The historian accepts only observations with GOOD quality and finite numeric or Boolean values. Boolean values are stored as 1 or 0 in the PostgreSQL NUMERIC value column. Source timestamps are preferred; received timestamps are used when the source does not provide one. A stale or disconnected source does not create repeated NULL history rows.

Zone 04 flow and valve indications are simulated process values, not physical measurements, and are therefore excluded from historian persistence. The historian uses the project's existing tables and does not create or modify Ignition sqlth_* tables.

Database migration and verification

After backing up the SCADA database, apply both registry migrations in chronological order:

psql -h <DB_HOST> -p <DB_PORT> -U <DB_USER> -d <DB_NAME> -f database/migrations/2026-11-02_common_historian_registry.sql
psql -h <DB_HOST> -p <DB_PORT> -U <DB_USER> -d <DB_NAME> -f database/migrations/2026-11-03_zone01_modbus_historian.sql

Both migrations are designed to be safe to rerun. The common registry migration registers Zone 02 and Zone 05 tags, corrects Zone 05 equipment ownership, and aligns Zone 02/05 flow units with the driver contract (gpm). The Zone 01 migration registers its eight pump, tank and valve observations, including the operator STOP latch. Zone 03 flow remains in L/min.

For the complete coverage list, SQL verification query and implementation notes, see docs/HISTORIAN.md.

REST API

Method Endpoint Purpose
GET /api API health response
GET /api/equipment Equipment configuration
GET /api/tags Tag configuration with equipment details
GET /api/tags/:tagName/value Latest stored value for a tag
GET /api/live Live CODESYS tag values
GET /api/zone01 Zone 01 Modbus TCP snapshot and communication quality
POST /api/zone01/command Zone 01 whitelisted AUTO/MANUAL/START/STOP/FAULT_RESET/RE-ENABLE commands
GET /api/zone02 Zone 02 observations
POST /api/zone02/command Zone 02 whitelisted command
GET /api/zone3 Zone 03 live values
POST /api/zone3/command Zone 03 whitelisted command
GET /api/zone4/live Latest in-memory MQTT reading and connection state
GET /api/zone4 Latest stored Zone 04 moisture reading
GET /api/zone4/state Zone 04 supervisory process state
POST /api/zone4/command Zone 04 mode command or local simulation command
GET /api/zone05 Zone 05 normalized BACnet observations
POST /api/zone05/command Zone 05 whitelisted BACnet command

Repository structure

index.html
css/                         HMI styles
js/                          Browser-side HMI logic
server/
  server.js                  Express API and service startup
  opcua.js                   CODESYS OPC UA client
  mqtt.js                    Zone 04 MQTT client and historian writes
  mqtt-discovery.js          UDP broker discovery responder
  zone04.js                  Zone 04 process simulation
  historian/
    historian.js             Shared PostgreSQL persistence service
  drivers/
    modbus/zone01.js         Zone 01 Modbus TCP client
    micro800/zone02.js       Rockwell Micro850 driver
    bacnet/zone05.js         Zone 05 BACnet/IP client
simulators/
  python-modbus-zone01/      Version-pinned Zone 01 Python simulator
database/                    PostgreSQL schema and database assets
PLC/                         PLC project assets
docs/                        Implementation notes, media and test evidence
  media/
    screenshots/             HMI theme screenshots
    testing/                 Functional test evidence
node-red/                    Node-RED flow assets retained in the repository

Getting started

Requirements

  • Node.js and npm
  • Python 3 for the Zone 01 process simulator
  • PostgreSQL
  • Mosquitto MQTT broker
  • CODESYS Control Win runtime with OPC UA enabled
  • Rockwell Micro850 accessible over EtherNet/IP for Zone 02
  • ESP8266 firmware and Wi-Fi configuration for Zone 04
  • BACnet/IP simulator host reachable over UDP 47809 for Zone 05

1. Install dependencies

npm install

2. Configure PostgreSQL

Create the building_irrigation database and apply the SQL schema in database/schema.sql. Configure the database connection using the environment variables read by server/database.js. Back up the database, then apply both historian registry migrations in order: database/migrations/2026-11-02_common_historian_registry.sql followed by database/migrations/2026-11-03_zone01_modbus_historian.sql.

3. Configure PLC and MQTT connections

Set the relevant environment variables before starting the service:

Variable Default Purpose
ZONE01_MODBUS_HOST 127.0.0.1 Zone 01 simulator host
ZONE01_MODBUS_PORT 1502 Zone 01 Modbus TCP port
ZONE01_MODBUS_UNIT_ID 1 Zone 01 Modbus unit identifier
ZONE01_MODBUS_POLL_MS 1000 Zone 01 polling interval
ZONE01_MODBUS_TIMEOUT_MS 2000 Zone 01 request timeout
ZONE02_PLC_IP 192.168.203.1 Micro850 address
MQTT_URL mqtt://localhost:1883 MQTT broker URL
MQTT_PORT 1883 Broker port advertised by discovery
MQTT_DISCOVERY_PORT 1884 UDP discovery listener
ZONE4_STALE_SECONDS 300 Zone 04 live-data freshness threshold
HISTORIAN_SAMPLE_INTERVAL_MS 5000 Maximum persistence rate per source for polled Zones 02, 03 and 05
ZONE05_BACNET_IP unset Optional unicast Who-Is target if subnet broadcasts are filtered
ZONE05_BACNET_PORT 47809 Zone 05 BACnet/IP UDP port
ZONE05_BACNET_DEVICE_INSTANCE 10005 Zone 05 BACnet Device instance
ZONE05_BACNET_CLIENT_PORT 47810 Local UDP port used by the SCADA BACnet client
ZONE05_BACNET_BROADCAST auto-detected Optional directed-broadcast IP override
ZONE05_BACNET_DISCOVERY_TIMEOUT_MS 3000 Wait time for an I-Am response
ZONE05_BACNET_DISCOVERY_RETRY_MS 5000 Delay before retrying device discovery
ZONE05_BACNET_POLL_MS 1000 Zone 05 polling interval

The CODESYS endpoint is currently defined in server/opcua.js as opc.tcp://127.0.0.1:4840.

4. Start the backend

npm start

The Express API listens on port 3000. The backend starts the Zone 01 Modbus TCP client, Zone 02 driver, OPC UA client, MQTT client, UDP broker-discovery responder and Zone 05 BACnet/IP client.

5. Open the HMI

Serve index.html through a local web server, such as the VS Code Live Server extension, and open it in a browser.

Check the API health endpoint at http://localhost:3000/api.

Zone 01 — Python water-process simulator and Modbus TCP

Zone 01 models a water storage tank filling process using a pump and valve. The canonical simulator source is maintained in Radfar/industrial-water-modbus-simulator. A version-pinned integration copy is included at simulators/python-modbus-zone01/ for reproducible Web SCADA development. Develop simulator logic in the standalone repository first, then synchronize the integration copy deliberately.

Start the simulator

Open a terminal in the Web SCADA repository root:

cd simulators/python-modbus-zone01
python -m venv .venv
.\.venv\Scripts\Activate.ps1
python -m pip install -r requirements.txt
python -m src.main

The simulator listens on 127.0.0.1:1502, Unit ID 1. Keep it running while the Node.js backend is active. In a second terminal, activate the same virtual environment and run:

python -m unittest discover -s tests -v
python -m src.client_check
python -m src.live_process_check

Node.js integration

The driver is server/drivers/modbus/zone01.js. It polls five coils, 14 discrete inputs, five holding registers and six input registers, and exposes:

  • GET /api/zone01 — normalized process snapshot and communication quality.
  • POST /api/zone01/command — whitelisted auto, manual, start, stop, faultreset and reenable commands.

A successful command response confirms that the Modbus write was accepted; the HMI separately observes the controller state and process feedback. The operator STOP latch is read at discrete input offset 13; RE-ENABLE is written to coil offset 4 and does not issue START. Analog values use a scale factor of 10.

The driver stores eight Zone 01 observations in the PostgreSQL historian. Back up the database, then apply database/migrations/2026-11-03_zone01_modbus_historian.sql. The migration registers the operator STOP latch tag as well as pump, tank and valve observations, and is safe to rerun.

Engineering limitations and security

This repository is a development and simulation testbed. Review these limitations before connecting real equipment:

  • The current CODESYS OPC UA client uses SecurityPolicy None and an anonymous session.
  • The Express API currently enables open CORS and does not implement operator authentication or authorization.
  • MQTT is configured for an unauthenticated, unencrypted private LAN.
  • UDP broker discovery is local-subnet broadcast discovery, not routed service discovery.
  • Zone 04 valve and flow behavior is simulated; the ESP8266 LED is only a firmware mode indicator.
  • Sensor calibration and physical field commissioning must be completed before treating moisture values as process-grade measurements.
  • PLC interlocks in the API improve operator feedback but do not replace safety logic implemented and validated in the controller.
  • Confirm network segmentation, access control, secure protocol configuration, fail-safe states and electrical protections before any production deployment.

Related repositories

Learning journal and engineering documentation

The docs/learning-journal.md is a maintained engineering notebook covering the system architecture, protocol integration decisions, normalized observation model, commissioning and regression testing, troubleshooting, known limitations and next experiments. It is written as a reusable learning resource as well as a project record.

License

MIT. See LICENSE.

HMI screenshots and test evidence

The HMI supports both dark and light themes. The screenshots are stored in docs/media/screenshots/:

Theme Screenshot
Dark mode hmi-dark-mode.png
Light mode hmi-light-mode.png

Web SCADA HMI — dark mode

Web SCADA HMI — light mode

Zone-level functional test procedures and results are documented in docs/testing. Supporting screenshots, Node-RED flow captures and edited demonstration videos are organized under docs/media. Large video files may be linked from an external host or attached to a GitHub Release rather than committed directly to the repository.