A custom browser-based SCADA/HMI for an industrial water-management testbed. The project brings together different controller and edge technologies behind one web monitoring interface.
The current implementation demonstrates five zone integrations:
- Zone 01 — Water storage tank process: Python process simulator exposed over Modbus TCP and polled by the Node.js driver.
- Zone 02 — Rockwell Micro850: EtherNet/IP communication using a Node.js driver based on
st-ethernet-ip. - Zone 03 — CODESYS: OPC UA communication with a CODESYS Control Win runtime.
- Zone 04 — IoT Edge: ESP8266 telemetry and bidirectional mode commands over MQTT.
- Zone 05 — BACnet/IP: an independent irrigation-device simulator accessed by a dedicated Node.js BACnet client driver.
The web application uses HTML, CSS and vanilla JavaScript on the frontend, Node.js and Express on the backend, and PostgreSQL for equipment, tag configuration and historical readings.
This is an engineering testbed. It is intended to explore controller integration, protocol handling, data acquisition, operator interaction and IT/OT architecture. It is not presented as a production-ready or safety-certified control system.
flowchart TB
subgraph FIELD["Field and control layer"]
Z1["Zone 01<br/>Python water-process simulator"]
Z2["Zone 02<br/>Rockwell Micro850"]
Z3["Zone 03<br/>CODESYS Control Win"]
Z4["Zone 04<br/>ESP8266 soil node"]
Z5["Zone 05<br/>BACnet/IP device simulator"]
end
subgraph COMM["Communication layer"]
MOD["Modbus TCP"]
EIP["EtherNet/IP"]
OPC["OPC UA"]
MQTT["MQTT / Mosquitto"]
BAC["BACnet/IP over UDP"]
end
subgraph APP["Custom Web SCADA"]
BE["Node.js / Express"]
FE["Browser HMI<br/>HTML / CSS / JavaScript"]
DB[("PostgreSQL")]
end
Z1 <-->|"Modbus TCP"| MOD
Z2 <-->|"EtherNet/IP"| EIP
Z3 <-->|"OPC UA"| OPC
Z4 <-->|"MQTT telemetry, status and commands"| MQTT
Z5 <-->|"BACnet/IP"| BAC
MOD <--> BE
EIP <--> BE
OPC <--> BE
MQTT <--> BE
BAC <--> BE
BE <--> FE
BE <--> DB
The backend acts as the integration layer between the controller-specific protocols and the browser HMI. The browser does not communicate directly with the PLCs.
| Zone | Technology | Integration | Current scope |
|---|---|---|---|
| Zone 01 | Python water-process simulator | Modbus TCP | Tank filling process, pump/valve model, live process values and whitelisted operator commands |
| Zone 02 | Rockwell Micro850 | EtherNet/IP | Live tag polling and whitelisted Boolean commands through the Node.js driver |
| Zone 03 | CODESYS Control Win | OPC UA | Live tag browsing and polling, operator commands and PLC-side process logic |
| Zone 04 | ESP8266 | MQTT | Soil-moisture telemetry, device status, AUTO/MANUAL commands and acknowledgements |
| Zone 05 | Simulated BACnet/IP device | BACnet/IP over UDP | Analog and binary process values, commandable Binary Outputs and process simulation |
| SCADA | Custom Web HMI | REST API | Unified monitoring, zone cards, operator controls and communication status |
The project also contains local process simulations. In particular, Zone 04 moisture telemetry is received from the ESP8266, while its valve command and flow indication remain simulated. The ESP8266 firmware's onboard LED indicates the selected firmware mode; it is not physical valve feedback.
| Layer | Technologies |
|---|---|
| Frontend | HTML5, CSS3, vanilla JavaScript |
| Backend | Node.js, Express |
| Database | PostgreSQL |
| Zone 01 protocol | Modbus TCP |
| Zone 02 protocol | EtherNet/IP |
| Zone 03 protocol | OPC UA |
| Zone 04 protocol | MQTT |
| Zone 05 protocol | BACnet/IP |
| MQTT broker | Mosquitto |
| Edge device | ESP8266 / Wemos D1 |
| PLC environments | Rockwell CCW / Micro800 and CODESYS |
- Multi-brand integration through separate protocol-specific backend drivers.
- Zone 01 Modbus TCP polling, tank/pump process simulation and explicit operator STOP-latch / RE-ENABLE semantics.
- Zone 02 Micro850 polling and controlled Boolean writes.
- Zone 03 OPC UA tag discovery from the CODESYS
GVL_SCADAvariable group. - Zone 03 command whitelist, pulse handling for edge-triggered commands and server-side interlock messages.
- Zone 04 MQTT telemetry ingestion directly by the Node.js backend.
- MQTT device status and command-result acknowledgement handling.
- UDP broker discovery for the Zone 04 ESP8266 on a shared IPv4 subnet.
- Shared PostgreSQL historian persistence for selected observations from Zones 01–05.
- Live data freshness handling, including
GOODandUNCERTAINquality states. - REST endpoints that separate the browser HMI from industrial protocol details.
- Zone 05 BACnet/IP polling, normalized observations and whitelisted AUTO/MANUAL/START/STOP/FAULT_RESET commands.
The Node.js driver is located at server/drivers/micro800/zone02.js.
- Uses the
st-ethernet-iplibrary. - Connects to the Micro850 using the configured PLC IP address.
- Polls configured Zone 02 tags at a one-second interval.
- Retries the connection after communication failure.
- Serializes PLC requests to avoid overlapping read and write operations.
- Uses a command whitelist. Start, Stop and Fault Reset are momentary pulse commands; Auto and Simulation Enable are level commands.
- Reads the permissive before accepting a Start command.
Default PLC address: 192.168.203.1. Set ZONE02_PLC_IP to override it.
The backend connects to CODESYS Control Win through OPC UA at:
opc.tcp://127.0.0.1:4840
The OPC UA client browses the GVL_SCADA variable group and polls discovered variables every second. Zone 03 commands are restricted to a whitelist:
| HMI command | PLC variable | Handling |
|---|---|---|
| Start | Z03_START |
300 ms pulse |
| Stop | Z03_STOP |
300 ms pulse |
| Fault Reset | Z03_FAULT_RESET |
300 ms pulse |
| Auto | Z03_AUTO |
Held TRUE |
| Manual | Z03_AUTO |
Held FALSE |
The PLC remains responsible for process logic. The API mirrors relevant interlocks to return clear operator feedback.
The Zone 04 data path in the current SCADA implementation is:
ESP8266 soil node
|
| MQTT telemetry
v
Mosquitto broker
|
v
Node.js MQTT client (server/mqtt.js)
|
+----> Live Zone 04 state / REST API
|
+----> PostgreSQL tag_values historian
The ESP8266 publishes a moisture payload every 15 seconds to:
- Telemetry:
zone4/soil01/data - Device status:
zone4/soil01/status - Mode command:
zone4/soil01/command - Command result:
zone4/soil01/command_result
The Node.js service validates incoming moisture values (0–100), updates the live value and asynchronously stores valid readings against the Z04_MOISTURE tag in PostgreSQL.
Historian quality records the validity at acquisition time. The live value can become UNCERTAIN when it exceeds the configured freshness threshold. The default threshold is 300 seconds and can be changed with ZONE4_STALE_SECONDS.
The HMI's AUTO/MANUAL mode changes are sent to the ESP8266 and require a command acknowledgement. START, STOP and RESET operate on the local Zone 04 process simulation; they do not actuate a physical valve.
The SCADA backend listens for UDP discovery requests on port 1884 and advertises the MQTT broker's IPv4 address and TCP port (default 1883). The ESP8266 broadcasts after repeated MQTT connection failures and stores a discovered broker address in LittleFS.
Discovery is limited to a shared broadcast-enabled IPv4 subnet. It does not cross routers or VLAN boundaries.
Zone 05 uses an independently runnable BACnet/IP device simulator in Radfar/bacnet-device-simulator. The SCADA backend acts as the BACnet client; the simulator does not depend on the SCADA database or HMI.
The driver is server/drivers/bacnet/zone05.js. It polls four Analog Inputs, two Binary Inputs and the AUTO-mode Binary Output, then exposes normalized observations through the SCADA API. Operator commands are restricted to AUTO, MANUAL, START, STOP and FAULT_RESET. START, STOP and FAULT_RESET are momentary requests: the driver writes ACTIVE at priority 8, then relinquishes the command slot so the request can be issued again. AUTO/MANUAL is a held command.
At startup, the driver sends BACnet Who-Is discovery requests to the local IPv4 subnet broadcast addresses (and optionally to a configured unicast IP), filtered for device instance 10005. It learns the simulator's current IP and UDP source port from its I-Am response, then starts polling. Discovery retries automatically if the device is not found. Because the simulator uses UDP 47809, the driver explicitly directs Who-Is broadcasts to UDP 47809 rather than the BACnet default UDP 47808. Discovery is intended for devices on the same broadcast-enabled subnet; routed networks require BBMD/Foreign Device Registration or a configured unicast target.
The simulator exposes:
| BACnet object | Instances | Purpose |
|---|---|---|
| Analog Input | 1–4 | Moisture, flow, valve position and tank level |
| Binary Input | 1–2 | Pump running and fault status |
| Binary Output | 1–4 | AUTO/MANUAL, START, STOP and FAULT RESET |
See the simulator README and its learning journal for the object map, process model, YABE commissioning notes and validation history.
The five zone integrations use a common historian writer and the existing PostgreSQL tags and tag_values tables. Protocol-specific drivers retain responsibility for acquisition; the shared service applies a consistent persistence contract and writes accepted observations to the same history table.
| Zone | Source | Persisted tags | Acquisition / storage behavior |
|---|---|---|---|
| Zone 01 | Python simulator / Modbus TCP | P01_FREQUENCY, P01_SPEED, P01_FLOW, P01_RUN_FEEDBACK, P01_FAULT, Z01_OPERATOR_STOP_LATCHED, T01_LEVEL, V01_POSITION |
Polled; sampled at the configured historian interval |
| Zone 02 | Micro850 / EtherNet/IP | All 17 tags in the driver registry | Polled; sampled at the configured historian interval |
| Zone 03 | CODESYS / OPC UA | Z03_MOISTURE, Z03_FLOW, Z03_VALVE, Z03_FAULT, Z03_AUTO |
Selected allow-listed variables; sampled at the configured interval |
| Zone 04 | ESP8266 / MQTT | Z04_MOISTURE |
Event-driven; a validated moisture message is stored when received |
| Zone 05 | BACnet/IP | Seven observations exposed by the BACnet driver | Polled; sampled at the configured historian interval |
The default sampling interval for Zones 01, 02, 03 and 05 is five seconds. Set HISTORIAN_SAMPLE_INTERVAL_MS to change it. Zone 04 remains event-driven and is not throttled by that interval.
The historian accepts only observations with GOOD quality and finite numeric or Boolean values. Boolean values are stored as 1 or 0 in the PostgreSQL NUMERIC value column. Source timestamps are preferred; received timestamps are used when the source does not provide one. A stale or disconnected source does not create repeated NULL history rows.
Zone 04 flow and valve indications are simulated process values, not physical measurements, and are therefore excluded from historian persistence. The historian uses the project's existing tables and does not create or modify Ignition sqlth_* tables.
After backing up the SCADA database, apply both registry migrations in chronological order:
psql -h <DB_HOST> -p <DB_PORT> -U <DB_USER> -d <DB_NAME> -f database/migrations/2026-11-02_common_historian_registry.sql
psql -h <DB_HOST> -p <DB_PORT> -U <DB_USER> -d <DB_NAME> -f database/migrations/2026-11-03_zone01_modbus_historian.sqlBoth migrations are designed to be safe to rerun. The common registry migration registers Zone 02 and Zone 05 tags, corrects Zone 05 equipment ownership, and aligns Zone 02/05 flow units with the driver contract (gpm). The Zone 01 migration registers its eight pump, tank and valve observations, including the operator STOP latch. Zone 03 flow remains in L/min.
For the complete coverage list, SQL verification query and implementation notes, see docs/HISTORIAN.md.
| Method | Endpoint | Purpose |
|---|---|---|
| GET | /api |
API health response |
| GET | /api/equipment |
Equipment configuration |
| GET | /api/tags |
Tag configuration with equipment details |
| GET | /api/tags/:tagName/value |
Latest stored value for a tag |
| GET | /api/live |
Live CODESYS tag values |
| GET | /api/zone01 |
Zone 01 Modbus TCP snapshot and communication quality |
| POST | /api/zone01/command |
Zone 01 whitelisted AUTO/MANUAL/START/STOP/FAULT_RESET/RE-ENABLE commands |
| GET | /api/zone02 |
Zone 02 observations |
| POST | /api/zone02/command |
Zone 02 whitelisted command |
| GET | /api/zone3 |
Zone 03 live values |
| POST | /api/zone3/command |
Zone 03 whitelisted command |
| GET | /api/zone4/live |
Latest in-memory MQTT reading and connection state |
| GET | /api/zone4 |
Latest stored Zone 04 moisture reading |
| GET | /api/zone4/state |
Zone 04 supervisory process state |
| POST | /api/zone4/command |
Zone 04 mode command or local simulation command |
| GET | /api/zone05 |
Zone 05 normalized BACnet observations |
| POST | /api/zone05/command |
Zone 05 whitelisted BACnet command |
index.html
css/ HMI styles
js/ Browser-side HMI logic
server/
server.js Express API and service startup
opcua.js CODESYS OPC UA client
mqtt.js Zone 04 MQTT client and historian writes
mqtt-discovery.js UDP broker discovery responder
zone04.js Zone 04 process simulation
historian/
historian.js Shared PostgreSQL persistence service
drivers/
modbus/zone01.js Zone 01 Modbus TCP client
micro800/zone02.js Rockwell Micro850 driver
bacnet/zone05.js Zone 05 BACnet/IP client
simulators/
python-modbus-zone01/ Version-pinned Zone 01 Python simulator
database/ PostgreSQL schema and database assets
PLC/ PLC project assets
docs/ Implementation notes, media and test evidence
media/
screenshots/ HMI theme screenshots
testing/ Functional test evidence
node-red/ Node-RED flow assets retained in the repository
- Node.js and npm
- Python 3 for the Zone 01 process simulator
- PostgreSQL
- Mosquitto MQTT broker
- CODESYS Control Win runtime with OPC UA enabled
- Rockwell Micro850 accessible over EtherNet/IP for Zone 02
- ESP8266 firmware and Wi-Fi configuration for Zone 04
- BACnet/IP simulator host reachable over UDP 47809 for Zone 05
npm installCreate the building_irrigation database and apply the SQL schema in database/schema.sql. Configure the database connection using the environment variables read by server/database.js. Back up the database, then apply both historian registry migrations in order: database/migrations/2026-11-02_common_historian_registry.sql followed by database/migrations/2026-11-03_zone01_modbus_historian.sql.
Set the relevant environment variables before starting the service:
| Variable | Default | Purpose |
|---|---|---|
ZONE01_MODBUS_HOST |
127.0.0.1 |
Zone 01 simulator host |
ZONE01_MODBUS_PORT |
1502 |
Zone 01 Modbus TCP port |
ZONE01_MODBUS_UNIT_ID |
1 |
Zone 01 Modbus unit identifier |
ZONE01_MODBUS_POLL_MS |
1000 |
Zone 01 polling interval |
ZONE01_MODBUS_TIMEOUT_MS |
2000 |
Zone 01 request timeout |
ZONE02_PLC_IP |
192.168.203.1 |
Micro850 address |
MQTT_URL |
mqtt://localhost:1883 |
MQTT broker URL |
MQTT_PORT |
1883 |
Broker port advertised by discovery |
MQTT_DISCOVERY_PORT |
1884 |
UDP discovery listener |
ZONE4_STALE_SECONDS |
300 |
Zone 04 live-data freshness threshold |
HISTORIAN_SAMPLE_INTERVAL_MS |
5000 |
Maximum persistence rate per source for polled Zones 02, 03 and 05 |
ZONE05_BACNET_IP |
unset | Optional unicast Who-Is target if subnet broadcasts are filtered |
ZONE05_BACNET_PORT |
47809 |
Zone 05 BACnet/IP UDP port |
ZONE05_BACNET_DEVICE_INSTANCE |
10005 |
Zone 05 BACnet Device instance |
ZONE05_BACNET_CLIENT_PORT |
47810 |
Local UDP port used by the SCADA BACnet client |
ZONE05_BACNET_BROADCAST |
auto-detected | Optional directed-broadcast IP override |
ZONE05_BACNET_DISCOVERY_TIMEOUT_MS |
3000 |
Wait time for an I-Am response |
ZONE05_BACNET_DISCOVERY_RETRY_MS |
5000 |
Delay before retrying device discovery |
ZONE05_BACNET_POLL_MS |
1000 |
Zone 05 polling interval |
The CODESYS endpoint is currently defined in server/opcua.js as opc.tcp://127.0.0.1:4840.
npm startThe Express API listens on port 3000. The backend starts the Zone 01 Modbus TCP client, Zone 02 driver, OPC UA client, MQTT client, UDP broker-discovery responder and Zone 05 BACnet/IP client.
Serve index.html through a local web server, such as the VS Code Live Server extension, and open it in a browser.
Check the API health endpoint at http://localhost:3000/api.
Zone 01 models a water storage tank filling process using a pump and valve. The canonical simulator source is maintained in Radfar/industrial-water-modbus-simulator. A version-pinned integration copy is included at simulators/python-modbus-zone01/ for reproducible Web SCADA development. Develop simulator logic in the standalone repository first, then synchronize the integration copy deliberately.
Open a terminal in the Web SCADA repository root:
cd simulators/python-modbus-zone01
python -m venv .venv
.\.venv\Scripts\Activate.ps1
python -m pip install -r requirements.txt
python -m src.mainThe simulator listens on 127.0.0.1:1502, Unit ID 1. Keep it running while the Node.js backend is active. In a second terminal, activate the same virtual environment and run:
python -m unittest discover -s tests -v
python -m src.client_check
python -m src.live_process_checkThe driver is server/drivers/modbus/zone01.js. It polls five coils, 14 discrete inputs, five holding registers and six input registers, and exposes:
GET /api/zone01— normalized process snapshot and communication quality.POST /api/zone01/command— whitelistedauto,manual,start,stop,faultresetandreenablecommands.
A successful command response confirms that the Modbus write was accepted; the HMI separately observes the controller state and process feedback. The operator STOP latch is read at discrete input offset 13; RE-ENABLE is written to coil offset 4 and does not issue START. Analog values use a scale factor of 10.
The driver stores eight Zone 01 observations in the PostgreSQL historian. Back up the database, then apply database/migrations/2026-11-03_zone01_modbus_historian.sql. The migration registers the operator STOP latch tag as well as pump, tank and valve observations, and is safe to rerun.
This repository is a development and simulation testbed. Review these limitations before connecting real equipment:
- The current CODESYS OPC UA client uses SecurityPolicy None and an anonymous session.
- The Express API currently enables open CORS and does not implement operator authentication or authorization.
- MQTT is configured for an unauthenticated, unencrypted private LAN.
- UDP broker discovery is local-subnet broadcast discovery, not routed service discovery.
- Zone 04 valve and flow behavior is simulated; the ESP8266 LED is only a firmware mode indicator.
- Sensor calibration and physical field commissioning must be completed before treating moisture values as process-grade measurements.
- PLC interlocks in the API improve operator feedback but do not replace safety logic implemented and validated in the controller.
- Confirm network segmentation, access control, secure protocol configuration, fail-safe states and electrical protections before any production deployment.
- Wireless Irrigation Edge — ESP8266 firmware, RF irrigation controller and edge-device assets.
- Water Process Integration Testbed — broader testbed architecture.
- OPC UA BACnet Gateway — separate protocol gateway project.
The docs/learning-journal.md is a maintained engineering notebook covering the system architecture, protocol integration decisions, normalized observation model, commissioning and regression testing, troubleshooting, known limitations and next experiments. It is written as a reusable learning resource as well as a project record.
MIT. See LICENSE.
The HMI supports both dark and light themes. The screenshots are stored in docs/media/screenshots/:
| Theme | Screenshot |
|---|---|
| Dark mode | hmi-dark-mode.png |
| Light mode | hmi-light-mode.png |
Zone-level functional test procedures and results are documented in docs/testing. Supporting screenshots, Node-RED flow captures and edited demonstration videos are organized under docs/media. Large video files may be linked from an external host or attached to a GitHub Release rather than committed directly to the repository.