Veton EV Charger — Loxone integration

A ready-to-import Loxone Config project that integrates a Veton EV charger (Phoenix Contact CHARX controller) into Loxone over Modbus/TCP, surfaced through Loxone's native Wallbox block.

This is the Loxone counterpart of the Home Assistant integration.

What changed recently — and what to re-check if you already deployed an earlier copy of this project — is in the changelog.

Screenshot

Loxone Wallbox visualization

Illustrative mockup of the Wallbox visualization. A real screenshot from the Loxone app/Config is welcome — drop a PNG into docs/images/ and update this.

What's included

  • Veton.Loxone — a Loxone Config project (Config 16.x) containing:
    • a Modbus server + device preconfigured with the CHARX register map,
    • the charger's metering + status mapped to inputs (energy, power, per-phase voltage & current, vehicle status, error code, release mode, SOC, last RFID card → the Wallbox block's Uid input),
    • write outputs for max charging current (X301) and the CHARX safety watchdog (X306 fallback current + X307 timer),
    • a Wallbox function block and a visualization page.
  • Veton-2CP.Loxone — the same project for a two-charging-point cabinet: one Modbus device carrying both points (CP1 on 1xxx, CP2 on 2xxx), with the Wallbox block, formulas and visualization mirrored per point.
  • MB_Veton.xml — a Modbus device template (the format the Loxone Library expects). Importing it adds the CHARX register map (13 sensors + 3 actuators) to a Modbus device in one step, without the rest of the project. Targets charging point 1 (1xxx). Three of the inputs need a manual validity-range fix after import — see After importing the template.
  • MB_Veton_CP2.xml — the same template for charging point 2 (2xxx), to add alongside the first one on a two-point cabinet.

Requirements

  • Loxone Miniserver Gen 2 with Loxone Config 16.0.6.10 or newer (the templates declare minVersion="16000610"). Both projects are saved as Gen 2 (Miniserver="2") and have only been tried there — Gen 1 is untested, not known to be unsupported.
  • A Veton / CHARX charger reachable on the LAN with Modbus/TCP enabled (port 502).
  • For Loxone to control the charging current (not just read the charger), the charger must be in external-control mode — see Who controls the current. As shipped, a Veton charger's own load management owns X301 and overwrites every value Loxone writes within seconds; reading works regardless.

Install

  1. Open Veton.Loxone in Loxone Config (or copy the Veton Modbus device + Wallbox page into your existing project).
  2. Select the Veton Modbus server and set its Address to your charger's IP (port 502). The project ships with this field blank on purpose.
  3. The register addresses target connector 1 (1xxx). For another connector, offset by connector × 1000 (connector 2 → 2xxx: 2120, 2232, 2244, 2250, 2301 …).
  4. Save to the Miniserver.
  5. Have the charger put in external-control mode (next section) — otherwise the Wallbox block's setpoint and pause never take effect.
  6. In the Loxone app select a charging mode for the Wallbox, and in Loxone Config set the block's Mode after unplugging vehicle parameter to a charging mode (e.g. Max. charging power) rather than Off — otherwise the block asks for 0 kW and the car is paused until someone picks a mode. The project ships with no mode selected and that parameter at its default. Note the block's allow input is shipped inverted and unwired (unconnected = charging allowed); wiring a "1 = allowed" signal to it without removing the inversion pauses the car.

Who controls the current: internal load management vs Loxone

A CHARX has its own load management built in, and a Veton charger ships with it active: the charging points belong to a CHARX load circuit and the internal manager rewrites the X301 setpoint of every point on each cycle. In that state everything this project reads works — power, energy, voltages, currents, vehicle status (Vc/Cac), error code — but every X301 write, the pause included, is overwritten within seconds. It looks as if the Wallbox block "does nothing".

Charger state Loxone reads Loxone X301 writes
Internal load management active (as shipped) work overwritten within seconds
External-control mode work take effect

For Loxone to control current, the charger has to be put in external-control mode: the charging points are detached from the CHARX load circuit so that nothing on the charger writes X301 any more. On a Veton-managed charger this is done by Veton — through the Veton app or backend — not from Loxone; ask for it when you commission the installation.

Two consequences of that mode:

  • The watchdog is the only protection left. Once nothing on the charger owns X301, a Miniserver that dies mid-session would leave the last setpoint in place forever. That is why the project ships the X306/X307 watchdog (below) and why it must stay in.
  • One energy manager per charger. Do not run another manager — Veton's solar/smart charging modes, a second EMS, a Home Assistant automation — on the same charger at the same time as Loxone. Two writers fight over X301, and the usual result is a car that ends up paused because the loser wrote 0 or 6 A last.

Register map (CHARX)

Function Register Operation
Counter active energy X250 read
Active power X244 read (5 s)
Voltage L1 / L2 / L3 X232 / X234 / X236 read
Current L1 / L2 / L3 X238 / X240 / X242 read
Vehicle status X299 read
Last RFID card X275 read (5 s), text
Charging release mode X120 read
SOC X264 read
Error code X293 read
Max charging rate (A) X301 write (FC06, re-sent every 60 s)
Watchdog fallback current (A) X306 write (FC06, re-sent hourly)
Watchdog timer (s) X307 write (FC06, re-sent every 60 s)
Charging release X300 not written — see below
Locking X303 not written — see below

Connector offset = connector × 1000, so connector 1 → registers 1xxx.

All values are FC03 holding-register reads / FC06 holding-register writes — the CHARX has no coils. Voltages, currents and power arrive in milli-units; the inputs carry a two-point correction that scales them:

Input Wire Displayed as Correction
Active power (X244) mW kW SourceValHigh="1000000" DestValHigh="1" (×1e-6)
Voltage / current mV / mA V / A 1 → 0.001, 100 → 0.1 (×1e-3)
Counter active energy (X250) Wh kWh 1 → 0.001, 100 → 0.1 (×1e-3)

Active power feeds the Wallbox block's power input, which is kilowatts — an earlier mW→W correction there made the block read 1000× high.

Why X300 / X303 are not written

Earlier versions of this project and of the templates wrote X300 (charging release) and X303 (locking). Both writes are gone as of 2026-09-03, for two independent reasons:

  1. Policy. Veton chargers ship with release mode = OCPP. The OCPP backend decides whether a car may charge (authorization, start/stop, billing, app visibility); an EMS only decides how fast, via X301 — which works in every release mode. Driving X300 means taking release away from OCPP, which breaks authorization, session/transaction records and app/backend visibility. See Veton-EMS-Integration/docs/modbus.md.
  2. They never worked anyway. Both were issued as ModbusCmd="5"FC05 Write Single Coil. A CHARX exposes holding registers only (FC03 read / FC06 write, FC16 for multi-register writes); it has no coils, so every one of those writes was rejected.

A standalone, non-OCPP deployment (no backend, release mode = Modbus) may legitimately need them. Add them by hand, as FC06 Write Single Register (ModbusCmd="6"), never FC05 Write Single Coil:

Function Register Values Requires
Charging release X300 0 = off, 1 = allow release mode = Modbus (X120 = 5)
Locking X303 0 / 1 locking mode = external

Do not do this on a Veton charger that talks to the Veton backend.

Note that pausing a car via X301 = 0 (see Pause semantics) does not take release away from OCPP either: OCPP still authorises the session and keeps recording it; the pause is simply a current cap of zero. The session stays open and resumes as soon as the cap goes back to 6 A or above.

Watchdog (X306 / X307)

The CHARX has a safety watchdog on the current setpoint: if nothing writes X307 for the number of seconds it holds, the charger falls back to the current in X306. It protects against a Miniserver that dies mid-session while X301 is sitting at a high value.

Register Ships as Meaning
X306 6 A fallback current when the timer expires (valid range 6–80 A; a value outside it withdraws the charging release)
X307 300 s the deadline; 65535 disables the watchdog

6 A is the IEC 61851 minimum, so a dead Miniserver slows the car down rather than cutting it off.

Loxone has no "keep-alive" primitive — what feeds the watchdog is the Modbus actuator's RepeatRate, which Loxone Config 17's help text for the Modbus output repeat property describes as the "interval in seconds, at which the output value is sent again". Whether a value of 0 is also re-sent has not been confirmed on a Miniserver. Either way the pause is written once, on change, and that write is what pauses the car; the 60 s re-send matters for the non-zero setpoints. X307 therefore ships with RepeatRate="60" — five re-sends of margin inside the 300 s window — and X306, which only needs to be present, with RepeatRate="3600". In the projects both registers are driven by a constant Formula block feeding an output ref; in the templates they are plain actuators you feed with a constant (6 and 300).

Actuator RepeatRate Why
X301 max current 60 s re-asserts the setpoint every minute (see below; the pause itself is written on change)
X306 fallback current 3600 s only needs to be present
X307 watchdog timer 60 s feeds the watchdog; five re-sends inside the 300 s window

RepeatRate must stay well below the X307 value — keep at least a 2× margin. If you raise it above the timer (or lengthen the timer's re-send interval), the watchdog fires during normal operation and pegs the charger at the 6 A fallback.

X301 is re-sent every 60 s as well (it used to be hourly). Some CHARX firmware has been seen to drop an externally written X301 back to 0 after a controller-side restart or a stray write; a client that re-sends its setpoint restores it within one RepeatRate interval, one that writes once an hour leaves the car at 0 for up to an hour.

Vehicle status (X299) → Wallbox Vc / Cac

X299 is one register holding two ASCII characters (IEC 61851 state), so it arrives in Loxone as a plain number:

State Meaning Register value
A1 / A2 no vehicle connected 16689 / 16690
B1 / B2 vehicle connected, not charging 16945 / 16946
C1 / C2 charging (no ventilation) 17201 / 17202
D1 / D2 * charging (ventilation required) 17457 / 17458
E0 CP short circuit / PE lost 17712
F0 EVSE fault / unavailable 17968
IN invalid state 18766

* D1 / D2 are defined by IEC 61851 (charging with ventilation required, CP at 3 V) but are not among the states CHARX actually emits on X299 — its register map lists only A1, A2, B1, B2, C1, C2, E0, F0, IN. The rows are kept because the formulas below bound their range harmlessly; do not expect to see them on a Veton charger.

The Wallbox block's Vc (Vehicle connected) and Cac (Charging active) inputs therefore need digital signals, not the raw register. The project derives both with Formula blocks fed from the Vehicle status input:

Block Formula On for
Vehicle connectedVc IF(I1>16944;IF(I1<17459;1;0);0) B/C/D — a car is plugged in
Charging activeCac IF(I1>17200;IF(I1<17459;1;0);0) C/D — the car is drawing

Both are 0 for A (no vehicle) and for the fault states E0/F0/IN. Wire the same two formulas if you build the project yourself from MB_Veton.xml.

RFID card → Wallbox Uid (user attribution)

The Last RFID card input reads X275, where the CHARX keeps the UID of the card last presented as ASCII text: 10 holding registers, big-endian, NUL-padded — 14 hex characters for a 7-byte card (04A1B2C3D4E5F6), 8 for a 4-byte card. It is read every 5 s as a Loxone String input (ModbusDataType="101", plain FC03, nothing is written) and wired straight to the Wallbox block's Uid (User ID) input in both projects. That is what should attribute a session to a person: the block's charge log records the Uid, its own Uid output echoes it, and the app's history should then show who charged (see Loxone's Wallbox block documentation). The block's price/cost outputs and charge log follow the Uid as well, so a mis-attributed session is also priced under that card holder — this matters on shared or tenant chargers.

To make it match, give each Loxone user a User ID typed exactly as the Last RFID card input shows it: uppercase hex, no separators (1A9998DA, 04A1B2C3D4E5F6; see the user's properties in Loxone Config). Note:

  • A 4-byte card gives 8 characters, a 7-byte card 14 — one person with two cards needs the Uid matched per card (one Loxone user per card, or a Uid mapping in front of the block).
  • The NFC tags stored on a Loxone user are not what the Wallbox block matches on; only the User ID property is.
  • Whether the match is case-sensitive is unverified — use uppercase, as the input shows it.
  • Per Loxone's documentation a session is reassigned to a driver who taps while the car is already plugged in only if that user has a valid User ID set; drivers without one are logged as whoever the block already held.

Privacy / security. The card UID is personal data and, on a CHARX with a UID whitelist, it is the authorisation credential itself. The input sits on the Wallbox visualisation page and the UID lands in the block's Uid output, the charge log and the Miniserver statistics — visible to every Loxone user with access to that page. Remove the input from the visualisation for non-admin users, and be aware that the Miniserver retains the UID in its logs/statistics.

What is measured and what is not:

  • The register contents were verified on production chargers in OCPP release mode (firmware 1.7.3) against the charger's own RFID event stream. Modbus, Always and the other release modes, and firmware 1.9.x, were not measured — a unit in Always mode read empty because no card had ever been presented to it.
  • X275 is sticky, and it only changes when a different card is tapped: the same driver tapping the same card produces no change at all, so in a single-driver household the Uid text is constant after the first tap. Whether the Wallbox block attributes each new session from the standing Uid value (sampled at session start) or only reacts to a change of Uid is not verified on the Loxone side. If the block samples Uid, the expected behaviour is: at plug-in the block first sees the previous card; once the new driver taps, the Uid changes and Loxone reassigns the session (User ID permitting); a session started without a tap — from the Veton app or remotely — inherits the previous card and is attributed (and priced) to that person. Verify it: in Loxone Config with a charger, tap the same card for two consecutive sessions and read the charge log (Lcl) — both sessions should carry that card; then tap two cards that differ only in their last characters and confirm both propagate.
  • The CHARX has a "reset last RFID" register (X308, write > 0). It was measured inert on firmware 1.7.3 (write acknowledged, X275 unchanged; not re-tested on 1.9.x), so this project deliberately does not write it; the sticky behaviour above is what you get.
  • Confirm the register count in Loxone Config. Loxone has no attribute for the length of a String input, so how many registers it reads is not documented. Open the project against a charger and look at the Last RFID card value. The full 14 characters of a 7-byte card means it reads enough. Fewer characters means Loxone reads fewer registers — the shortened value may not be unique (the first byte of a 7-byte NXP card is always 04), so check for collisions and set the users' IDs to what the input actually shows. More than 10 registers spills the read into X285X294 (connection time, energy, error bitfield): the symptom is characters appended after the UID, so the value never equals the card and User ID matching fails, or the input going offline (Modbus exception) if the span crosses an unmapped address. In both cases the sensor needs a shorter read — please report it. While you are there, run the checklist compactly: the String connector shows as text; the user wire survives save/reload; the value shows the full UID; two similar cards both propagate; the same card twice attributes both sessions.

Setpoint: three-phase (default) vs single-phase (mono)

The Wallbox block asks for power (kW); X301 wants current (A). A Formula block converts, and the project ships two of them on the Program page:

Block Formula Inputs For
3 fase IF(I1>0;MIN(MAX(INT((I1*1000)/(400*1,732));6);80);0) I1 = Wallbox outLimit [kW] three-phase 400 V — wired by default
mono IF(I1>0;IF(I2>100;MIN(MAX(INT((I1*1000)/MAX(I2;100));6);80);6);0) I1 = Wallbox outLimit [kW], I2 = Voltage of phase L1 [V] single-phase — shipped on the page, deliberately not wired

Only one of the two may be connected to Max Charging Rate I. Both were connected in earlier versions, so two blocks wrote conflicting values into the same register, last-writer-wins. mono was disconnected on 2026-09-03 and 3 fase kept.

Both formulas are pause-aware: the outer IF(I1>0;…;0) passes a 0 kW request through as 0 A, and any request above 0 kW is converted, truncated and clamped to X301's valid 6–80 A range. What that 0 does is the next section.

Pause semantics: what a 0 kW request does

The Wallbox block puts its target power (outLimit, "Tp") to 0 when the session is paused, when load shedding leaves nothing for the car, when the block is Off, or when no mode allowing charging is active. On a CHARX, writing X301 = 0 withdraws the charging release (documented in Veton-EMS-Integration/docs/modbus.md) — the charger tells the car to stop drawing. The project uses exactly that as the pause:

Wallbox target power X301 written Charger Car
0 kW 0 A withdraws the charging release pauses
> 0 kW 6 … 80 A keeps / restores the release, caps the current charges, resumes after a pause

Earlier versions clamped every request to a 6 A floor, so "pause" from the Wallbox block meant "charge at 6 A". Now a pause is a pause. Things to know before relying on it:

  • No charging mode selected, or Mode after unplugging vehicle = Off, is the #1 reason a car will not charge. The block outputs a target power of 0 whenever no charging mode is active, and the project ships with no mode selected and that parameter at its default. So a fresh import in external-control mode writes X301 = 0 and re-sends it every 60 s: the car never starts. The same happens after anything the block treats as an unplug — including the charger being unreachable for a while: the Vehicle status input reads 0, Vc drops, the session ends and the block falls to its mode-after-unplug. Select a mode in the app and set Mode after unplugging vehicle to a charging mode (e.g. Max. charging power), see Install step 6. Also: the block's allow input ships inverted and unwired (unconnected = charging allowed) — wiring a "1 = allowed" signal there without removing the inversion pauses the car.
  • Some EVs go to sleep during a long pause and do not resume when current is offered again; they need an unplug/replug. Loxone has no way to send a wake pulse to the car, so if a car on your site behaves like that, avoid long pauses for it (raise the block's Min. charging power parameter, default 4.16 kW, instead of pausing).
  • If the Miniserver dies during a pause, the watchdog fallback (X306 = 6 A) resumes the car at 6 A after 300 s. That is fail-safe toward slow charging, by design — a dead Miniserver never leaves a car stranded, but it also does not keep it paused.
  • Firmware 1.9.1 and ISO 15118. The Phoenix Contact CHARX 1.9.1 release notes list a known issue: during an ISO 15118 session (plug-and-charge / high-level communication), a load-management setpoint below 6 A opens the contactor under load — and the 0 A pause is such a setpoint. On 1.9.1 with 15118-capable cars, either disable 15118 on the charging point or go back to a never-pausing setpoint: remove the outer IF(I1>0;…;0) from both formulas, i.e. use MIN(MAX(INT((I1*1000)/(400*1,732));6);80) for 3 fase and IF(I2>100;MIN(MAX(INT((I1*1000)/MAX(I2;100));6);80);6) for mono (the 2026-09-03 forms, which floor a 0 kW request at 6 A). The fix script's --check will then report the formulas as not pause-aware — expected on such a site.
  • X301 = 0 is the only zero this project ever writes, and only while the Wallbox block asks for 0. Every other path — a voltage reading that is missing, a request too small to convert, the watchdog fallback — stays at 6 A or above. If you edit the formulas, keep it that way.

The setpoint truncates, it never rounds up

X301 is a whole-ampere register, so the value Loxone computes has to become an integer somewhere. Left to the register write it would round, and rounding up asks the charger for more than the Wallbox block budgeted: 7.4 kW works out to 10.68 A, which rounds to 11 A ≈ 7.62 kW — about 0.22 kW over budget, and up to ~0.5 A in the worst case. On a site whose load management handed out exactly 7.4 kW, that overshoot is real current on a real fuse.

Both formulas therefore wrap the division in INT() (Loxone's documented "integer function (removes decimals)"), so the setpoint truncates: 7.4 kW → 10 A, 11 kW → 15 A, 22 kW → 31 A. Loxone never asks the charger for more power than the Wallbox block asked for. The one deliberate exception is the bottom of the range: a request above 0 kW but below 6 A still lands on the 6 A floor, because the CHARX accepts nothing between 0 and 6 A — 6 A is the IEC 61851 minimum. A request of exactly 0 kW is not floored: it becomes the 0 A pause described above.

Single-phase (mono)

On a single-phase supply, swap the two blocks in Loxone Config: disconnect 3 fase from Max Charging Rate I, then connect mono's output to it instead. mono already ships with the pause, the clamp, the truncation and a divide-by-zero guard:

IF(I1>0;IF(I2>100;MIN(MAX(INT((I1*1000)/MAX(I2;100));6);80);6);0)

I2 is the measured Voltage of phase L1 input, not a nominal 230 V — and a measured input reads 0 whenever the charger is unreachable, the poll has not landed yet, or the contactor is open. Dividing by that would yield 0 A, and 0 is precisely the value that withdraws the charging release — an accidental pause. The inner IF guard means "only compute a setpoint when we have a plausible mains reading": 100 V is below every real single-phase supply (230 V nominal, 207–253 V at ±10 %) and above every partial or absent reading, so anything at or under it falls back to the 6 A minimum instead of dividing (the divisor is floored at 100 as well, in case Loxone evaluates both branches). The outer IF(I1>0;…;0) is the deliberate pause, same as in 3 fase.

If you would rather not depend on a live reading at all, use the nominal voltage and drop the guard with it: IF(I1>0;MIN(MAX(INT((I1*1000)/230);6);80);0), leaving I2 unconnected.

Loxone formulas use a comma as the decimal separator (1,732) and a semicolon as the argument separator.

Multiple charging points

Veton.Loxone covers one charging point (connector 1). For a two-point cabinet there is a ready-made variant: Veton-2CP.Loxone.

Register addresses are connector × 1000 + register:

Charging point Register base e.g. max current
1 1xxx 1301
2 2xxx 2301
3 3xxx 3301

Veton-2CP.Loxone (two charging points)

One CHARX controller is a single Modbus TCP endpoint, so both charging points live in one Modbus device (Veton - Charger) — CP1 on 1xxx, CP2 on 2xxx — rather than two devices sharing an address. Everything downstream is mirrored per point:

Per charging point CP1 CP2
Modbus sensors / actuators 13 + 3 @ 1xxx 13 + 3 @ 2xxx
Wallbox block Wallbox CP1 Wallbox CP2
Vc / Cac formulas CP1 Vehicle connected / CP1 Charging active CP2 …
Error status block CP1 Error CP2 Error
Vehicle-status tracker CP1 Vehicle status CP2 Vehicle status

Set the Modbus server Address once — both points share it.

For the charger I/O alone, MB_Veton.xml covers connector 1 and MB_Veton_CP2.xml covers connector 2. For a third point and beyond, copy either template and add 1000 to every ModbusAddress.

Modbus device template (MB_Veton.xml)

For just the charger I/O (no full project), use the Modbus device template:

  1. In Loxone Config, select the Modbus Extension (or Modbus TCP) in the periphery tree → ribbon Device templates → Import template → pick MB_Veton.xml. (Or drop it straight into Loxone Config's template folder — C:\ProgramData\Loxone\Loxone Config <ver>\Templates\Comm\ on Config 17, …\LoxoneConfig <ver>\ENG\Comm\ on older builds. The filename must keep the MB_ prefix.)
  2. Add the device, set the charger's IP (port 502), then wire the inputs/ outputs to a Wallbox block. The template's Last RFID card input (X275, String, 5 s) goes to the block's Uid input — see RFID card → Wallbox Uid; it needs no range fix.

The template targets charging point 1 (registers 1xxx); for more points, offset every address by connector × 1000 (see above).

This is also the file to submit to the official Loxone Library (curated by Loxone).

After importing the template (required)

A Loxone Modbus device template has no way to express an input's validity range — MinVal/MaxVal are not template attributes (Loxone's own shipped templates use none). Three inputs therefore need their range widened by hand, once, in Loxone Config after the device is added. The full .Loxone projects already ship with all three applied; only template users have to do this.

Input Set Why
Counter Active Energy (X250) Maximum value 10000100000000 It is a lifetime kWh counter. A charger past 10 000 kWh exceeds the default ceiling and the input stops reporting — the charger on the bench already reads 12 182 kWh, so the old ceiling is already exceeded.
Vehicle status (X299) Minimum 0, Maximum 65535 The value is two ASCII characters packed into one 16-bit register, i.e. ≈ 16 000–19 000 (A1 = 16689 … IN = 18766) — out of range under the default limits, so Vc/Cac never go true.
Error Code (X293) Minimum 0, Maximum 4294967295 X293/X294 is a 32-bit error bitfield, not a fault number: bit N has the mask 2**(N-1). So bit 14 alone is already 8192, bit 15 is 16384 — past the stock ±10000 ceiling — and a bit 22 fault is 2 097 152, 200× over it. Under the default limits the input silently stops showing real faults: every fault from bit 15 up is out of range, so the fault display reads clean while the charger is in error.

In Loxone Config: select the input in the periphery tree → PropertiesMinimum value / Maximum value. Redo this after re-importing the template.

Notes

  • Ships with the Modbus server IP blank and the document APPKEY cleared — set your own on import.
  • The charger must be in external-control mode before any X301 write (setpoint or pause) sticks; as shipped, the CHARX internal load management overwrites it within seconds. Reads work either way. See Who controls the current.
  • Nothing here writes charging release. The projects and templates only write X301 (current cap) and X306/X307 (watchdog); release stays with OCPP. See Why X300 / X303 are not written.
  • A 0 kW request from the Wallbox block pauses the car (X301 = 0); any request above 0 kW resumes it at 6–80 A. X301 = 0 is the only zero this project writes. See Pause semantics for the caveats (sleeping EVs, the watchdog resuming at 6 A, firmware 1.9.1 with ISO 15118).
  • No charging mode selected, or Mode after unplugging vehicle = Off, is the #1 reason a car will not charge: the block then asks for 0 kW and the car is paused until someone picks a mode. Select a mode in the app and set that parameter to a charging mode (Install step 6).
  • X301 is re-sent every 60 s, so a setpoint that the charger drops is re-asserted within a minute (whether a 0 is re-sent too is unconfirmed; the pause is written on change either way).
  • Template users: do the three manual range fixes above, otherwise the energy counter, the vehicle-status derived Vc/Cac signals and the error-code display will not work.
  • The X301 setpoint truncates rather than rounds, so Loxone never asks the charger for more power than the Wallbox block budgeted. See The setpoint truncates, it never rounds up.

License

MIT — free to use and modify.