With such settings, the PID controller does not change, the value is always 30, even the ppm codes change. The input value is ppm and the output is the motor speed in %.
I can see what's happening here. The PID output has experienced severe integral windup, with the I-term at approximately -2,137,000 while your output should be between 30-100.
The Problem
Your system is a direct acting controller: higher CO2 should result in higher ventilation output. However, the standard PID formula with positive gains is designed for reverse acting systems (like cooling, where higher temperature → higher cooling → lower temperature).
With your current setup:
When CO2 (960) is above your target setpoint, the error becomes negative
Positive Ki with negative error causes the I-term to accumulate negatively
This pushes the output down instead of up
The Solution
For a direct acting system (higher input → higher output), you need negative gains:
Parameter Current Change to
Kp 1 -1
Ki 0.1 -0.1
Kd 0.05 -0.05
Steps to fix
Turn off Auto Mode
Set Kp = -1, Ki = -0.1, Kd = -0.05
Verify your Setpoint is your target CO2 level (e.g., 600-800 ppm)
Ensure Windup Protection is enabled
Set Start Mode to "Zero start" or "Startup value"
Turn on Auto Mode
This resets the PID and starts fresh with the correct gain signs. The output should now increase when CO2 rises above your setpoint.
How can I make the fan speed not increase so rapidly, because my room has a range from 400 to 2500, so at 1000, I understand it shouldn't be 100%, or will it reduce the fan speed when the set value is reached?
That P value alone is already 3x your entire output range (30-100)! So it instantly hits the maximum.
How to fix: Lower your gains
For your input range (400-2500 ppm) and output range (30-100%), try these values as a starting point:
Parameter Current Recommended
Kp -1 -0.03
Ki -0.1 -0.005
Kd -0.05 -0.01
Setpoint ? 600-800 (your comfort target)
What this gives you
With Kp = -0.03 and setpoint = 700:
At 1000 ppm: P = -0.03 × (700-1000) = +9 → modest increase
At 2500 ppm: P = -0.03 × (700-2500) = +54 → stronger push toward max
At 400 ppm: P = -0.03 × (700-400) = -9 → pushes toward minimum
The Ki (integral) will slowly adjust the output over time to reach and maintain your setpoint. The Kd (derivative) dampens rapid changes.
Tuning tips
Start with Ki = 0 and Kd = 0, tune Kp first until the response speed feels right
Then add small Ki to eliminate steady-state error
Add Kd only if you see oscillation
After changing gains, turn Auto Mode off and on again (with Zero start) to reset the I-term.
P = -8.34 → Kp is correctly negative ✓
i_delta = +1.9 → Ki is still positive ✗
I = 100 → stuck at maximum
You only changed Kp to negative, but Ki is still positive. This causes the I-term to grow in the wrong direction until it hits the limit (100).
What's happening
Output = P + I + D = -8.34 + 100 + 0 = 91.66
The I-term is stuck at maximum and won't come down because Ki has the wrong sign.
Fix
Turn OFF Auto Mode
Change your gains - ALL must be negative:
Parameter Your current Change to
Kp -0.03 (or similar) Keep as is
Ki +0.1 ← wrong! -0.005
Kd (check this too) -0.01
Set Start Mode to "Startup value"
Set Startup Value to 50 (middle of your 30-100 range)
Turn ON Auto Mode
This resets the I-term to a neutral value and ensures all gains work in the same direction.
Why all gains must have the same sign
For a direct-acting system (higher CO2 → higher fan speed):
Kp negative: When CO2 > setpoint, P pushes output UP ✓
Ki negative: When CO2 stays above setpoint, I gradually pushes output UP ✓
Kd negative: When CO2 is rising, D pushes output UP ✓
If you mix positive and negative gains, the P/I/D components fight each other.
It's working if I see the logs. your PPM stays stable as , and your I-term is slowly decreasing, so it will stabilize at some point when your input starts decreasing towards your setpoint. Now it's up to you to tune the parameters to make it move quickly but within bounds.
That's hard for me to guess, because I do not have the information of your system, and you need to trail-and-error. I would suggest finding some youtube videos or ask an AI agent to support you.
Activity
amgstone commentedon Feb 2, 2026
bvweerd commentedon Feb 2, 2026
Please disable windup protection and retry.
If this does not help please upload the diagnostics file obtained from the integration.
amgstone commentedon Feb 2, 2026
disable windup protection
bvweerd commentedon Feb 2, 2026
As said, please upload the diagnostics if it doesn't help.
amgstone commentedon Feb 3, 2026
config_entry-simple_pid_controller-01KGFMNGP4HH0REEVEQGFR511A-1.json
bvweerd commentedon Feb 3, 2026
Thanks for the detailed diagnostics!
I can see what's happening here. The PID output has experienced severe integral windup, with the I-term at approximately -2,137,000 while your output should be between 30-100.
The Problem
Your system is a direct acting controller: higher CO2 should result in higher ventilation output. However, the standard PID formula with positive gains is designed for reverse acting systems (like cooling, where higher temperature → higher cooling → lower temperature).
With your current setup:
The Solution
For a direct acting system (higher input → higher output), you need negative gains:
Parameter Current Change to
Kp 1 -1
Ki 0.1 -0.1
Kd 0.05 -0.05
Steps to fix
This resets the PID and starts fresh with the correct gain signs. The output should now increase when CO2 rises above your setpoint.
amgstone commentedon Feb 3, 2026
max ppm- 1 004 ppm, Rekuperator PID Output-100%.
How can I make the fan speed not increase so rapidly, because my room has a range from 400 to 2500, so at 1000, I understand it shouldn't be 100%, or will it reduce the fan speed when the set value is reached?
bvweerd commentedon Feb 3, 2026
With your current settings (Kp = -1) and assuming setpoint = 700 ppm:
That P value alone is already 3x your entire output range (30-100)! So it instantly hits the maximum.
How to fix: Lower your gains
For your input range (400-2500 ppm) and output range (30-100%), try these values as a starting point:
Parameter Current Recommended
Kp -1 -0.03
Ki -0.1 -0.005
Kd -0.05 -0.01
Setpoint ? 600-800 (your comfort target)
What this gives you
With Kp = -0.03 and setpoint = 700:
The Ki (integral) will slowly adjust the output over time to reach and maintain your setpoint. The Kd (derivative) dampens rapid changes.
Tuning tips
After changing gains, turn Auto Mode off and on again (with Zero start) to reset the I-term.
amgstone commentedon Feb 3, 2026
config_entry-simple_pid_controller-01KGFMNGP4HH0REEVEQGFR511A-2.json
something is not working properly, with ppm the situation does not change so sharply and the fan speed increases to the maximum. 50 ppm higher than the setpoint and the speed is already 91%
bvweerd commentedon Feb 3, 2026
Looking at your PID contributions:
You only changed Kp to negative, but Ki is still positive. This causes the I-term to grow in the wrong direction until it hits the limit (100).
What's happening
Output = P + I + D = -8.34 + 100 + 0 = 91.66
The I-term is stuck at maximum and won't come down because Ki has the wrong sign.
Fix
This resets the I-term to a neutral value and ensures all gains work in the same direction.
Why all gains must have the same sign
For a direct-acting system (higher CO2 → higher fan speed):
If you mix positive and negative gains, the P/I/D components fight each other.
amgstone commentedon Feb 3, 2026
and did everythin
config_entry-simple_pid_controller-01KGFMNGP4HH0REEVEQGFR511A-3.json
g as you wrote.
bvweerd commentedon Feb 5, 2026
It's working if I see the logs. your PPM stays stable as , and your I-term is slowly decreasing, so it will stabilize at some point when your input starts decreasing towards your setpoint. Now it's up to you to tune the parameters to make it move quickly but within bounds.
amgstone commentedon Feb 5, 2026
suggest initial parameters for a more or less stable system for my needs
bvweerd commentedon Feb 6, 2026
That's hard for me to guess, because I do not have the information of your system, and you need to trail-and-error. I would suggest finding some youtube videos or ask an AI agent to support you.