Modbus TCP Simulator

A lightweight Modbus TCP server for testing HMIs, SCADA systems, data loggers and your own Modbus client code without real hardware. Define named points in a JSON file, give them moving signals (sine, ramp, random walk, counters), and poke values by hand from an interactive console.

Written in plain .NET 8 with no third party packages. Runs on Windows, Linux, macOS and Docker.

build .NET 8 License: MIT

Features

  • Full protocol coverage for testing: function codes 01, 02, 03, 04, 05, 06, 15, 16, 22 (mask write) and 23 (read/write multiple)
  • Correct exception responses: illegal function, illegal data address, illegal data value, with spec quantity limits
  • All four tables, full address range: coils, discrete inputs, holding registers, input registers (0..65535)
  • Typed points: bool, uint16, int16, uint32, int32, float32, with ABCD or CDAB word order and an engineering scale factor
  • Live signals: constant, ramp, sine, square, random walk, counter
  • Interactive console: read and write any address, set named points, pause signals, watch traffic as hex
  • Multiple clients: each connection handled independently, split and pipelined frames handled correctly
  • Headless mode: runs fine in Docker or as a background process

Quick start

git clone https://github.com/softechies/modbus-tcp-simulator.git
cd modbus-tcp-simulator
dotnet run --project src/ModbusTcpSimulator -- --config samples/tank-farm.json --port 5020

Then point any Modbus client at 127.0.0.1:5020. For example with mbpoll (note it uses 1 based addresses):

mbpoll -a 1 -r 1 -c 2 -t 3:float -1 127.0.0.1 -p 5020   # Tank1 Level as float32

Or with Python and pymodbus:

from pymodbus.client import ModbusTcpClient
client = ModbusTcpClient("127.0.0.1", port=5020)
print(client.read_holding_registers(2, count=1).registers)   # Pump Speed
client.write_coil(1, True)                                  # start Pump2

Docker

docker build -t modbus-sim .
docker run --rm -p 502:502 modbus-sim

Console commands

> points
Name                   Table  Addr Type              Value  Signal
Tank1 Level %          ir        0 Float32          57.257  Sine
Tank2 Level %          ir        2 Float32          10.481  Ramp
Tank1 Temp C           ir        4 Int16              21.7  Random
Pump Speed rpm         hr        2 UInt16             1450
Pump1 Run              coil      0 Bool                 ON
...

> get hr 0 4
hr[0] = 17046  (int16  17046, 0x4296)
hr[1] =     0  (int16      0, 0x0000)
hr[2] =  1450  (int16   1450, 0x05AA)
hr[3] =     1  (int16      1, 0x0001)

> set hr 3 2
> set coil 1 on
> setp Tank1 Level % 95        # pauses that point's signal so the value sticks
> resume Tank1 Level %
> verbose on                   # log every request/response as hex
> stats

Type help for the full list.

Config file

{
  "port": 5020,
  "tickMilliseconds": 200,
  "points": [
    {
      "name": "Tank1 Level %",
      "table": "ir",              // coil | di | hr | ir
      "address": 0,               // zero based
      "dataType": "float32",      // bool | uint16 | int16 | uint32 | int32 | float32
      "wordOrder": "ABCD",        // ABCD (high word first) or CDAB
      "scale": 1,                 // raw = value * scale, e.g. 10 for tenths
      "value": 50,                // initial value
      "signal": { "type": "sine", "min": 20, "max": 85, "periodSeconds": 120 }
    }
  ]
}
Signal Behaviour Uses
constant Holds min Placeholder you change by hand
ramp Linear min to max over the period, then restarts Filling tanks, test sweeps
sine Smooth wave between min and max Temperatures, levels
square max for half the period, min for the rest Run/stop states, valve cycles
random Random walk of up to step per tick, clamped to the range Realistic noisy sensors
counter Adds step every period, wraps after max Production counts, totalisers

See samples/tank-farm.json for a complete example.

Addressing

Addresses in this tool are zero based protocol addresses, which is what goes on the wire. Many HMI and SCADA tools use 1 based "register numbers" instead:

Table Here Typical tool notation
Coil 0 coil 0 00001
Discrete input 0 di 0 10001
Input register 0 ir 0 30001
Holding register 0 hr 0 40001

Command line

modbus-sim [options]
  -c, --config <file>   JSON config with points and signals
  -p, --port <port>     TCP port (default 502)
  -b, --bind <address>  IP to listen on (default 0.0.0.0)
  -v, --verbose         log every request and response as hex

The simulator answers every unit id and echoes it back, like most Modbus TCP devices.

Project layout

src/ModbusTcpSimulator/
  Protocol/    request handler (PDU in, PDU out), function and exception codes
  Server/      TCP listener and MBAP framing
  Data/        the four data tables
  Simulation/  typed points, signals, config loading
  Cli/         interactive console commands
tests/         protocol, codec, signal and TCP integration tests
samples/       example configs

Tests

dotnet test

License

MIT