What to Validate
Complete calculation against IEEE 1584-2018 Annex D.1 worked example.
IEEE 1584-2018 Reference
Test Inputs (from D.1-D.7)
- Ibf = 15 kA
- Voc = 4.16 kV
- Gap = 104 mm
- Working distance = 914.4 mm (36")
- Arc duration = 197 ms
- Enclosure = 508mm × 508mm × 508mm (20" cube)
- Config = VCB
Expected Results (fill in from Annex D)
Acceptance Criteria
What to Validate
Complete calculation against IEEE 1584-2018 Annex D.1 worked example.
IEEE 1584-2018 Reference
Test Inputs (from D.1-D.7)
Expected Results (fill in from Annex D)
Acceptance Criteria
tests/test_ieee1584.py