AI field electrician in shadow mode: Meta Muse Spark reads a real transfer-switch drawing, an information-gain planner picks each measurement, and safety tiers enforced in code gate every action.

Topics

Resources

Stars

0 stars

Watchers

0 watching

Forks

Repository files navigation

ProbeForge: the name in brushed metal with an orange lightning bolt

Live demo: probeforge.swd07.com

ProbeForge

CI

An AI field electrician in shadow mode: it reads the drawing of a real transfer switch, chooses its own measurements and finds the root cause, under safety limits enforced in code.

Built during the Meta Global AI Developer Hackathon, Oct 26 to Nov 4, 2026 (Indie Developer track). Solo project by Eduard Kharaev.

Hybrid v2 mid-run on a transfer switch fault: the next planned reading ringed and labelled next A and next B on the drawing, the note that the drawing is our redrawing, the planner's next step with the causes each result keeps, the candidate faults, the pipeline log and the UPS clock draining

Hybrid v2 mid-run on a saved drawing read: the planner's next reading is ringed on the drawing ("next A", "next B") and its card lists the causes each possible result keeps; the log lists every reading with its policy check, and the UPS clock drains 30 s per reading.

The problem

A data center loses utility power. The generator starts, but the automatic transfer switch does not move the critical load onto it. The UPS carries the load, and it has minutes left. A technician has to find the fault from the controller's lights, a drawing and a meter, without making things worse: no bypassing interlocks, no paralleling sources, no operating the switch by hand under load.

Power is the leading cause of such outages: power issues accounted for 45 percent of respondents' most impactful outages in 2025, and one in five outages now exceeds $1 million in total costs (Uptime Institute, Annual Outage Analysis 2026, as reported by The Register, 13 May 2026).

What ProbeForge does

ProbeForge simulates that situation on an ASCO Series 300 Group G transfer switch (our redrawing of wiring diagram 978741) with a hidden fault, and lets three diagnosticians work on it through the same tools and the same safety policy:

  • Agent: Muse Spark with tool calling picks every reading and action itself and keeps an explicit hypothesis list.
  • Hybrid v2: Muse Spark in three roles, each checked by deterministic code: it reads the drawing into a netlist (checked against the documented ASCO transfer sequence), repairs the reading when a measurement contradicts it (a repair is accepted only if the fault-free sequence still holds), and explains the result to the technician (structured output, then a code check that the text names the diagnosed part, and the root cause before any part it damaged). Between those roles an information-gain planner chooses the readings.
  • Engineer mode: a human does the same job on the same screen, optionally with the planner's suggestion (shadow mode, the trace is marked assisted).

Every reading or action passes the policy first. Anything risky waits for a human approval; some actions are never allowed. The UPS clock drains 30 s per reading, and a correct diagnosis after the UPS ran out is shown as what it is: critical load lost.

Result card after the same run: verdict Correct, the injected fault revealed, UPS time left at diagnosis, the Compare button with the cost of its re-runs, Muse Spark's explanation for the technician, and the diagnosed part outlined on the drawing

The same run's result: the diagnosed part outlined on the drawing, the injected fault revealed only now, the UPS time left at diagnosis, Compare with what its re-runs cost, and Muse Spark's explanation for the technician.

Quick start

Try it online: https://probeforge.swd07.com (no install). The public demo shows the transfer switch bench, with the limits described in docs/HOW_TO_USE.md (section 8).

Run it locally

Requires Python 3.11+, uv and Node 20 or newer (tested with Node 24). It runs from a checkout of this repository (not as an installed package). The commands use the lockfiles.

uv sync --frozen
cd web && npm ci && npm run build && cd ..
echo META_API_KEY=your_key_here > .env
uv run python -m probeforge.server --port 8000

Open http://127.0.0.1:8000 (the transfer switch bench opens by default), choose Agent, Hybrid or Engineer, pick a fault (or a random one) and press Start. Without a key, PROBEFORGE_OFFLINE=1 runs Engineer mode and the hybrid on the saved drawing read without model calls. Tests: uv run pytest. Check the committed results offline: uv run python scripts/verify_results.py. The UI step by step: docs/HOW_TO_USE.md. Architecture: ARCHITECTURE.md; scripts: scripts/README.md. License: MIT (LICENSE). It covers our code and redrawings, not ASCO documents (NOTICE).

Architecture

flowchart LR
  subgraph bench ["Simulated bench (hidden fault)"]
    S["ATS simulator: sources, Group G controller, mechanism, UPS"]
  end
  T["Tool API: panel, meter, isolate, manual check, repeat transfer, repair"]
  P["Safety policy in code: allowed / approval / strong approval / never"]
  A["Agent: Muse Spark, tool calling"]
  H["Hybrid v2: information-gain planner"]
  D["Drawing sheets"] --> R["Muse Spark: read"] --> C{"Documented ASCO sequence check"}
  C -- "contradicted" --> RP["Muse Spark: repair"] --> C
  C -- "holds" --> H
  H --> E["Muse Spark: explain"] --> K{"Code check: names the part, root cause first"}
  A --> P
  H --> P
  P --> T --> S
  U["Human: approvals, Engineer mode"] --> P
  K --> W["Web UI: live drawing, log, result"]
  A --> W
Loading

The agent and the planner never see the injected fault: tests check the agent's prompt for all 118 catalog faults and that the UI events carry the fault only in the final result. Components, data flow and invariants: ARCHITECTURE.md. Every design decision with its evidence: DECISIONS.md.

How Meta tooling is used

All model calls go to muse-spark-1.3 through the Meta Model API (Chat Completions); the key stays server-side.

  • Reading a real drawing. Muse Spark transcribes seven crops of the original ASCO drawing 978741 (drawing areas only; the crops are not in the repository, the saved reads are) into a netlist. The transcription is checked against the transfer sequence documented in the Group G User's Guide (8 of 8 events in order) before any planning; where it fails, Muse Spark is asked to repair the region that explains the failure. On the saved read, relay contacts were right 4/8 before repair and 8/8 after two accepted repairs (D34); on the 28-case holdout no reading contradicted it, so no repair ran (results).
  • Tool calling. The agent drives the bench with tools (panel, meter, isolation, manual operation check, repeat transfer, repair requests, diagnosis) and updates its hypotheses through a tool after each reading, at low reasoning effort.
  • Structured output. The technician explanation is strict JSON with the part to act on as an enum of the netlist's part ids, rendered and checked in code, with one retry and a template fallback (D41, D42). Holdout: 28/28 passed (15 model texts, 13 templates for insufficient information). Since D47 code also puts a fixed isolation sentence before every repair instruction, and the check rejects a fixed list of unsafe wordings (bypassing, paralleling sources, skipping the lockout, energized work, re-energizing before a repair; D50). It narrows what the model can say; it is not a safety review of the text.
  • Chat Completions vs Responses. On the 12 dev cases Chat got 10/12 part-level correct and 0 confidently wrong, Responses 8/12 and 1, with 32 % fewer readings and 13 % lower uncached cost. We kept Chat: it found the root cause of the burnout chain where Responses stopped at the burnt coil (D38).

Safety policy

Enforced in code (src/probeforge/ats/policy.py), never only in the prompt. The full table is in the UI and in docs/ATS_MODEL.md.

Tier Examples
Allowed read the panel, event log, metering; measure voltage; resistance only with both sources isolated
Approval isolate the sources while the load is not powered; manual operation check (isolated only); repairs (isolated only)
Strong approval isolate a powered load; restore or repeat a transfer after a Transfer Failure; must cite a reading and state the policy's facts to the approver
Never bypass an interlock, parallel the sources, operate the handle under load

Blocked attempts return to the diagnostician as an error and are counted. In the holdout run the batch approver approved the approval tier and denied every strong approval.

Engineer mode: the approval card Isolate sources, with the policy's reason, the technician's reason and Deny / Approve buttons

Engineer mode: isolating the sources for an ohmmeter check waits for a human approval, with the reason on the card.

Results

One holdout run on 28 faults nobody picked by hand, against the 12 dev cases (full results; every cited run with its per-case traces: results/runs/):

Agent dev Agent holdout Hybrid v2 dev Hybrid v2 holdout Baseline holdout
Part-level correct 10/12 17/28 10/12 18/28 18/28
Confidently wrong 0/12 3/28 0/12 0/28 0/28
Insufficient information 2/12 11/28 2/12 13/28 13/28
Latent faults (correct = insufficient information) 3/3 3/3 3/3
Correct diagnosis before the UPS ran out n/a 12/28 10/12 15/28 15/28
Readings per case 13.2 14.5 3.8 2.6 2.7
Cost per case (actual) $0.095 $0.12 $0.009 $0.006 free

The baseline is the same planner on the true netlist: a ceiling for the planner, not a peer. Hybrid v2 matched its verdict on every holdout case. The 3 latent cases count in both "correct" and "insufficient information" (for them, insufficient information is the correct answer).

How the holdout was protected: everything it depends on was frozen first: 13 fingerprints covering the agent, tools, policy, bench, fault catalog, scoring and the hybrid (D45). The 28 cases were then sampled by a fixed seed from the fault catalog, excluding every dev fault, their twins and every fault already run in the UI (the one chain case, the other side of the burnout chain, shares its burnt coil with a dev case), and committed with their sha256 before any run (holdout.yaml). The run refused to start unless the file, its hash, the commit and the fingerprints matched. One run; the first 5 cases were a smoke test for technical failures only; no changes, no reruns; $3.54 of a $6 cap (D46). The fingerprints cover the listed components, not every dependency. The exact code of that run is the tag holdout-2026-10-31.

After the holdout, an external review found three defects in frozen code: the agent could not request powered-load isolation in a schema-valid way, caller arguments could count as meter evidence, and the explanation check accepted repair wording without isolation first. They are fixed with new fingerprints; offline, the hybrid's and the baseline's tool logs and diagnoses are identical before and after (120 of 120); the agent was not re-run (D47, results).

What it shows:

  • The agent was confidently wrong 3 times on unseen faults: two guesses among position-feedback candidates, and once it named the burnt coil (the consequence) instead of the misadjusted cut-off contact (the root cause).
  • 8 position-feedback faults ended in insufficient information for all three: the load is powered, isolating it needs strong approval, and the batch rule denied it. That is the policy working as designed; such a fault needs a planned outage.
  • The agent made 2 correct diagnoses after the UPS had run out; the hybrid never lost the load.

Limits and disclosures

  • The Hybrid v2 pipeline (drawing crops, reading conventions, the sequence checks, the repair messages and the explanation step with its check) was developed on this one drawing and the 12 dev cases. Generalization to other drawings is not shown.
  • The page shows the explanation for the technician tidied for display: a step prefix the model repeated is removed, readings it spelled out are shown as numbers with units, and hyphens are restored in compounds it wrote apart ("de-energized", "fault-free", "cut-off contact"). The run record keeps the model's text unchanged, and the explanation check scores that text (D52).
  • The explanation check verifies the repair order, the isolation sentence and that the cited readings were taken, but not how the text interprets a reading: two recorded explanations misread the manual-check reading and passed.
  • A strong-approval request must cite executed instrument readings; the policy checks that they were executed, not when they were taken (a reading from before a repair can be cited for the restore).
  • The ATS model, the assumptions and the troubleshooting sheet have not been reviewed by an electrical engineer.
  • Undocumented behaviour (Transfer Failure and Position Error timing, coil burnout time, coil resistance, the UPS rule) is labelled as an assumption with a status and a source where one exists, S1 to S7 in docs/ATS_MODEL.md. The UPS autonomy (10 min) is a simulation parameter within the published data center range.
  • The bench, the fault catalog and the holdout sampler are written by the same author; independence rests on seeded catalog sampling after the freeze, not on an outside test set.
  • One run per diagnostician, 28 holdout cases: small samples. The agent's dev numbers were recorded before the UPS load-lost fields existed.
  • One UI agent run (Oct 31, 11:33) used a random fault that was not recorded; it may be in the holdout pool. Nothing was tuned on it.
  • Saved drawing reads are real earlier Muse Spark reads, labelled as saved in the UI; nothing shown as live is prerecorded.

Equipment provenance

ASCO Series 300 Group G automatic transfer switch, 200 A, 208 V, 3 phase 4 wire, service entrance. The netlist (scenarios/circuits/asco_300g_978741.yaml) and the drawing shown in the UI (docs/asco_300g_978741.svg) are redrawn by us from ASCO wiring diagram 978741 and the Group G Controller User's Guide; every part and net carries its source. It is our redrawing, not the official drawing. What the models see differs: the agent gets an image rendered from our netlist plus the netlist as text; Hybrid v2's read step gets crops of the original drawing from the author's local copy of the submittal package (drawing areas only, never the cover pages or title blocks; listed with their hashes in docs/ATS_MODEL.md). Those crops are not in the repository, so a live re-read needs your own copy of the drawing; the saved reads let everything else run without it. The original documents are in the public ASCO / Schneider Electric technical library: Series 300 service entrance drawings, Group G wiring, outline and mounting data. Vendor PDFs are not in this repository.

Where it started: the motor starter

ProbeForge began on a simulated star-delta reversing motor starter (17 components, 91 faults). On its clean holdout of 38 visible faults the agent got 30/38 at pole level against 25/38 for a half-split baseline and 35/38 for the information-gain ceiling (results). It showed the approach works and that a textbook circuit is too easy, so the work moved to real equipment. That stage, its hybrid pipeline and its findings: docs/LEVEL1.md. The UI still offers it under "Motor starter" when run locally; the public demo shows the transfer switch bench only.

Cost and spend guard

Live UI runs and the maintained paid scripts go through a metered client that reserves an upper bound in a local ledger before every model call and settles it with the actual cost afterwards, so concurrent runs cannot pass on the same balance and a run that fails midway still records what it spent (eval/spend.py, eval/metered.py). Batches stop at $110 of the $130 total; the rest is for live UI runs on the author's machine, with a daily cap. Every live UI run stops at $0.75. In public mode a separate ledger starts at $0 on the server with its own total ($30 by default) and the same daily cap, and calls are capped at 10,000 completion tokens (2.1x the largest call in the recorded runs). The ledger is per machine and not committed; the provider-side spend limit on the key is the real cap. The author's ledger recorded about $56 for the whole project.

Demo video credits