Define conservative cooldown behavior during sensor faults #4
Follow-up from PR #1 interlock review. This is important safety-policy work, but it is not a Phase-0 merge blocker.
Problem
Current blocked() cooldown behavior only commands fan output when sensors_ok() is true, and sensors_ok() requires all required temperature sensors to be valid and finite.
That means a single failed sensor can suppress cooldown fan output even when another valid sensor still reports residual heat.
Example:
chamber sensor: open/invalid
outlet sensor: valid and hot
case sensor: valid and hot
heater: correctly blocked
current fan policy: 0% because the aggregate sensor-valid condition fails
The safest behavior is not yet established. We should not casually invent a policy before considering airflow hardware, residual-heat behavior, reboot/brownout handling, and fault recovery.
Decision required
Define the product-level cooldown/fault policy for:
one sensor invalid while another valid sensor indicates residual heat;
all temperature sensors unavailable or implausible;
sensor failure while actively heating;
normal stop versus latched fault;
reboot/brownout during cooldown;
fan failure during required cooldown;
minimum/maximum cooldown duration if temperature evidence is unavailable;
recovery and fault-clear prerequisites.
Acceptance criteria
Conservative cooldown behavior is explicitly documented.
The policy distinguishes trustworthy remaining temperature evidence from complete sensor uncertainty.
Interlock/fan behavior is updated if required.
Host tests cover the chosen fault-state transitions.
Bench/HIL tests demonstrate cooldown behavior on release-intent hardware.
The safety verification record identifies retained evidence and its location.
Phase-0 model update from PR #1 corrective safety review (commit 8459894): blocked/fault cooling now stops only when every required sensor is valid, finite, and at or below the cooldown release threshold. Any partial or complete temperature uncertainty requests 100% fan output, and any remaining valid hot sensor remains actionable; a valid sensor can independently latch its sensor-specific overtemperature trip even when another sensor has failed. Host tests cover each invalid status, NaN/Inf, partial invalid+hot evidence, complete uncertainty, and fully valid/cool release. Physical fan behavior, reboot/brownout policy, and release-intent HIL/bench validation remain outstanding, so this issue stays open.
Pre-actuation gate: cooldown_required producer and lifecycle
Identified during review of the staged PID control work in #9 (stacked on #7). This is an explicit pre-actuation gate, not a current actuation defect: there is still no heater actuator in the firmware.
Requirement
Before any real heater actuator can exist, Jump Jet must have a validated producer and lifecycle for cooldown_required.
Invariant
Removing heater authorization, or transitioning from delivered heating to OFF, must not by itself make recently delivered heat thermally safe for OTA.
Current state
The OTA guard requires both !heater_authorized and !thermal_management_required. "Heater unauthorized" is deliberately not treated as "thermally safe".
Add staged PID control architecture #9 adds regression tests proving the staged Stage 1 → controller → Stage 2 pipeline preserves thermal_management_required across both stages when cooldown_required or fault_requires_thermal_management is asserted, so the staged window cannot create a false OTA-safe condition.
However, nothing in production asserts cooldown_required yet. So today, a transition from delivered heating directly to OFF with no producer active would leave the final state OTA-eligible. That is moot while no actuator exists, but must be closed before one does.
Out of scope here
This does not define cooldown thresholds, durations, or temperature criteria. Those require Phase 3 evidence and belong to the policy decisions already listed in this issue.
Activity
danielbrownjr commentedon Aug 29, 2026
Phase-0 model update from PR #1 corrective safety review (commit 8459894): blocked/fault cooling now stops only when every required sensor is valid, finite, and at or below the cooldown release threshold. Any partial or complete temperature uncertainty requests 100% fan output, and any remaining valid hot sensor remains actionable; a valid sensor can independently latch its sensor-specific overtemperature trip even when another sensor has failed. Host tests cover each invalid status, NaN/Inf, partial invalid+hot evidence, complete uncertainty, and fully valid/cool release. Physical fan behavior, reboot/brownout policy, and release-intent HIL/bench validation remain outstanding, so this issue stays open.
danielbrownjr commentedon Sep 24, 2026
Pre-actuation gate:
cooldown_requiredproducer and lifecycleIdentified during review of the staged PID control work in #9 (stacked on #7). This is an explicit pre-actuation gate, not a current actuation defect: there is still no heater actuator in the firmware.
Requirement
Before any real heater actuator can exist, Jump Jet must have a validated producer and lifecycle for
cooldown_required.Invariant
Removing heater authorization, or transitioning from delivered heating to OFF, must not by itself make recently delivered heat thermally safe for OTA.
Current state
!heater_authorizedand!thermal_management_required. "Heater unauthorized" is deliberately not treated as "thermally safe".thermal_management_requiredacross both stages whencooldown_requiredorfault_requires_thermal_managementis asserted, so the staged window cannot create a false OTA-safe condition.cooldown_requiredyet. So today, a transition from delivered heating directly to OFF with no producer active would leave the final state OTA-eligible. That is moot while no actuator exists, but must be closed before one does.Out of scope here
This does not define cooldown thresholds, durations, or temperature criteria. Those require Phase 3 evidence and belong to the policy decisions already listed in this issue.