feat(safety,devices): Phase 4 – PR 4-G Akku-Steuerung über das Gate mit den Invarianten aus ADR-0013 - #33
Open
PXLJAKE wants to merge 16 commits into
Open
feat(safety,devices): Phase 4 – PR 4-G Akku-Steuerung über das Gate mit den Invarianten aus ADR-0013#33PXLJAKE wants to merge 16 commits into
PXLJAKE wants to merge 16 commits into
Conversation
…line, battery identity and mode (WP10) - BatteryAction is the full desired state; None = the adapter's baseline value of that field (resolve_battery_action), capabilities per field, live field ranges, round-up quantisation - core.identity.battery_identity / battery_identity_token (asset id, adapter template, role entities, site SoC and battery power, modbus hub and unit id) - operation.battery_mode (additive): a battery or site put that changes the identity drops it to shadow, an import always resets it, a restore keeps it only for the recorded identity; a full operation put cannot raise it - BatterySettings.modbus (hub, unit id, byte order, heartbeat, fallback timer) and fallback_measured (additive); mode providers report the battery mode Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…s pure functions (WP10) - safety/battery.py: BatteryActuator protocol (capabilities, live ranges, settle, heartbeat, hardware-fallback prepare), BatteryContext from the resolved target, live flows, the band of a fresh plan interval, the live price and the import limit - B1 floor never below the reserve nor the user's own floor (rounded up to the step), B2 grid charging bounded by battery, adapter, band and import headroom (0 when any bound is unknown), B3 only from a fresh planned interval inside the policy at the live price and below max SoC, B4 discharge lock only when planned, B5 import limit, B6 live ranges and no cap above the baseline, B9 capabilities; BatteryWatch for a frozen battery power / SoC (B8) - property tests (hypothesis) for every claim; catalogue keys en/de - the gate still rejects battery intents (wired in the next step) Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…and kostal_modbus (WP10) - suncore/devices/battery behind the gate's BatteryActuator protocol: capabilities from the mapped roles, live ranges from the entity attributes, write only on change, read-back, release to the baseline; generic numbers / mode select / force-charge switch - kostal_plenticore: Battery:MinSoc only (no set-point over REST), settle 35 s for the silent REST write and the 30 s poll, the usage-mode select read only - kostal_modbus: §3.5 via modbus.write_register (a write of this adapter only, through the rate-limited ServiceCaller, never a read-only action): float32/U32 words in the configured word order, refuses unless register 1080 reads 2, arms 1284/1286/1288 before any limit, heartbeat re-write, release writes the battery's own limits explicitly - core.battery_adapter (adapter spec, mode meanings, modbus roles) so devices import only core; templates generic.battery, kostal.plenticore, kostal.plenticore_g3_modbus (driver, register map, sources, unverified lists) with conformance scenarios; boundary rules cover the battery adapters and their arm_fallback / keep_alive writes Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…riants (WP10) - the blanket safety.battery_not_supported rejection now applies only without a battery adapter (observe-only, no model) or to another asset id; intents for the configured battery pass the battery invariants B1-B6/B9 against the takeover baseline (None = baseline), the live flows, the band of a fresh plan interval, the live import price and the import limit, the adapter's precondition and capabilities, write only on change - takeover arms and reads back the hardware fallback first; the mode is capped at assisted while the fallback is not measured; mandatory read-back, three failures trip and release - the accepted state is a lease re-judged by poll() every tick: shadow, a watchdog pause, stale inputs or any failed invariant release it; heartbeat only while it holds; a change outside SunCore is an override; a release of an adapter without fallback is read back - check_battery(): frozen battery power / SoC (B8) pause the battery scope and release - every Phase 3 release path covers the battery (emergency stop, shutdown, mode to shadow, site/device trip, reconnect, crash recovery, re-mapped battery via its identity) Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…nts (WP10) - controller.battery.BatteryIntents: grid_charge_max_w -> grid_charge_w (rounded down, within the battery and adapter limits; an all-or-nothing switch only at full power), discharge_lock -> max_discharge_w 0 or a min-SoC floor at the live SoC rounded up (never below the reserve), nothing planned -> ReleaseAction only while the gate holds something (None = baseline) - only a fresh plan interval counts (core.control.battery_band_now, shared with the gate); reasons controller.battery.* incl. grid_charge_unsupported (Kostal REST) for the plan view - against oscillation: intents only on change, power hysteresis, a min-SoC lock moves only a full step after the SoC, one intent per interval, repeats after shadow/proposed every 15 min, property test with flapping bands - a held forced grid charge is never surplus for the consumers Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…pi/v1/operation/battery (WP10)
- ControlStack builds the battery adapter through safety.wiring (observe-only when it cannot be
built or a device uses the id "battery"), hands the gate its BatteryGateConfig (identity,
model, effective reserve, effective grid-charge policy, fallback_measured, the tick's plan,
the live price), runs the battery watch every tick and gives the controller the adapter's
capabilities, ranges and what the gate holds
- runtime: battery section loaded and applied (rebuild, resubscribe, identity rule), devices'
reserve guard = effective_reserve_pct with a model, set_battery_mode with the identity token
- control state: battery (identity, capabilities, modes incl. the assisted cap, limits, held,
baseline, wanted, reasons, pause, last decision); PUT /api/v1/operation/battery {mode,
identity} (404 observe-only, 409 stale identity); OpenAPI and frontend types regenerated
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
- sim/inverter.py: the inverter's own self-consumption control as the fallback, min-SoC floor judged on the BMS reading, BMS drift at night, REST refresh lag and silent REST failures, Kostal §3.5 registers through modbus.write_register with the fallback timer (1288), 1080 external control, hang (frozen power, writes ignored); fake HA publishes its numbers and modbus sensors and routes number.set_value / modbus.write_register to it - runner: battery wiring from the scenario (generic, kostal.plenticore, kostal_modbus templates) - scenarios modbus_heartbeat_lost, battery_reserve_drift, kostal_rest_reserve, inverter_hang_battery (cloud flicker, write counts), grid_charge_price_level (real planner, controller and gate in automatic mode) - gate fixes found by the scenarios: the heartbeat is timed from the write (not the read-back), a new takeover supersedes the check of the previous release Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…013 invariants (WP10) - ADR-0011 addendum: control-safety sign-off - the battery_not_supported rejection is lifted only for intents to the configured battery adapter that pass B1-B9; it stays for observe-only batteries and every other asset id - architecture §4: the battery path (controller band -> BatteryAction, gate invariants, hardware fallback, lease and heartbeat, release paths) - plan phase-4 deviations for PR 4-G; templates README (battery templates, driver, register map, hardware_fallback) Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…ostal Modbus and REST Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…line reads back (review B1, M3) - the battery release keeps the runtime under control with the ORIGINAL baseline until a read-back shows it (or the user set a third value, which is kept without a write); a failed release write or a read-back that still shows SunCore's state is retried with back-off (30 s doubling to 10 min) - also during an emergency stop - and never adopted as a baseline; while it is pending no takeover, write or heartbeat happens (latched in the runtime, so a healthy watchdog tick cannot clear it) - a failed battery write is pending, so a release never mistakes SunCore's partial state for the user's - generic/kostal_plenticore release raises on an unavailable entity instead of reporting success, and restores the user's own select option / switch state (review minor 4) - regression tests from the reviewer's probes (many check_battery ticks, stuck lock, new takeover, unavailable REST number); inverter_hang_battery asserts the latch until hang_to Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…seline and fallback values (review M1, M2, minors 1, 2, 3, 8) - B4/B5 judge ctx.target, the resolved state that is written and heartbeated: an inherited max_discharge_w = 0 or floor is a discharge lock (forced grid charging is none); property test with arbitrary baselines; regression test from the reviewer's probe - takeover_baseline(): kostal_modbus takes None fields from the battery's own limits (1076/1078), never from possibly stale 1280/1282 - kostal_modbus arms 1284/1286 with the larger of the model's and the own limits and prepared() compares with the values it wrote (UNVERIFIED: 1076/1078 dynamics); register 5 is a role and must match the configured byte order before any write (minor 1) - the lease ends when the adapter refuses (no heartbeat into a refusing inverter, minor 2) and when no fresh plan interval covers the held state any more, also without import (minor 8) - the settle wait after arming runs outside the gate lock (an emergency stop is not delayed) and the invariants are judged again under the lock right before apply() (minor 3) Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…oC sets a floor, realistic battery sim (review minors 5, 6, 7) - battery identity includes fallback_measured: marking the fallback measured lifts the assisted cap, so the battery drops to shadow until re-confirmed with the new token (minor 5) - the controller reads the SoC only with Quality.OK (minor 7) - sim: REST refresh 30 s against the 35 s settle, modbus sensor scan lag (10 s), stale 1280/ 1282 left by an earlier controller; a §3.5 takeover is never skipped because the registers merely show the value (not in force); price jump inside the grid-charge window ends the lease (scenario test); the hang latch holds until hang_to (minor 6) Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…ation addendum for the PR 4-G review fixes - ADR-0013 addendum (no decision changed): invariants in safety/battery.py, B4/B5 on the written state, release completes on read-back, kostal_modbus baseline/fallback, identity includes fallback_measured, reserve behaviour (maintainer default) answered - plan deviations: review fixes 2026-10-26; architecture §4: release latch and lease ends Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
… write for a user value The release's third-value shortcut compared the read-back only with last_written or pending_action. A pending write landing after an earlier confirmed one, or a partly applied multi-field write, was finalised as the user's choice and SunCore's own limit stayed on the battery. - DeviceRuntime.attempted keeps the resolved target of every write SunCore sent or attempted while under control (saved before apply, cleared when control ends). - safety.battery.user_changed_fields: a field is the user's only if it differs from the baseline and from every own value; restore_target keeps those fields and restores the rest. The release writes that state and waits for the read-back; the lease's override check uses the same rule. - A user change found during the release sets the override hold (next 04:00) like the lease's override path. - Generic adapter: the user's select option and switch state are remembered only before the first write attempt, never after a failed or partial apply. Regression tests: reviewer probe 3, mixed multi-field case, partial write without user change, late write on the lease, hold, driver retry; hypothesis properties for user_changed_fields/restore_target. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…-check fixes Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
…te lands When the lease's read-back shows an older SunCore state instead of the held one, the gate now re-writes the held state through the evaluated write path (B1-B9 on the current inputs, read-back) and releases the battery if that write is not accepted. Adapters without a heartbeat would otherwise run the older, unjudged state until the lease ended. STATUS notes the accepted edge case (a user value equal to an own value is reset at release) for the 4-H user docs. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01VHXsfH6PkT62o9idByAd6e
5 tasks done
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.This suggestion is invalid because no changes were made to the code.Suggestions cannot be applied while the pull request is closed.Suggestions cannot be applied while viewing a subset of changes.Only one suggestion per line can be applied in a batch.Add this suggestion to a batch that can be applied as a single commit.Applying suggestions on deleted lines is not supported.You must change the existing code in this line in order to create a valid suggestion.Outdated suggestions cannot be applied.This suggestion has been applied or marked resolved.Suggestions cannot be applied from pending reviews.Suggestions cannot be applied on multi-line comments.Suggestions cannot be applied while the pull request is queued to merge.Suggestion cannot be applied right now. Please check back later.
Gestapelt auf #31 (PR 4-F). Die Basis wird nach dem Merge der Vorgänger umgestellt.
Was
WP10 aus
docs/plans/phase-4.md, nach ADR-0013 (vom Maintainer am 2026-10-19 angenommen; die Statuszeile ist auf dem 4-A-Branch eingetragen).BatteryActionbeschreibt Grenzen, keine Sollwerte.Nonebedeutet „Wert vor der Übernahme“ (Baseline).battery_identitymit Identitäts-Token.operation.battery_mode. Schatten ist Standard; ein Import, eine Neuzuordnung oder eine Änderung vonfallback_measuredsetzt zurück auf Schatten.suncore/devices/battery/, Aufruf nur über das Gate):generic: über HA-Entitäten (Number, Select, Switch).kostal_plenticore(REST): Min-SoC als Reserve bzw. Entladesperre. Es gibt keinen Lade-Sollwert, Netzladen wird nur angezeigt. Wartezeit 35 s für den Read-back. Stille Schreibfehler werden über den Read-back erkannt.kostal_modbus: Grenzen aus §3.5 übermodbus.write_register(nur in diesem Adapter, nie read-only).fallback_measuredgesetzt ist (HardwareUNVERIFIED).safety.battery_not_supportedgilt nur noch ohne Adapter. Akku-Intents laufen durch die Invarianten B1–B9.inverter_hang_battery,battery_reserve_drift,grid_charge_price_level,kostal_rest_reserve,modbus_heartbeat_lost.PUT /api/v1/operation/batterymit{mode, identity}; Akku im Regelstatus. Keine UI (kommt in 4-H).Warum
Exit-Kriterium von Phase 4: „Akku-Steuerung im Schattenmodus, dann assistiert“ (Roadmap). Grundlage ist die Strategie „Akku möglichst voll“ des Maintainers. Netzladen soll nur geplant, bewusst und begrenzt passieren.
Wie getestet
./scripts/check.shgrün: 4651 Python-Tests, 219 Frontend-Tests, Abdeckung 96 %. markdownlint ohne Fehler.Risiken
UNVERIFIED).UNVERIFIED. Die Number-Entitäten sind in HA standardmäßig deaktiviert.Safety-Review
control-safety (Implementierung) und reviewer (unabhängig, zwei Re-Checks): freigegeben, mit einem offenen Minor-Punkt, der in diesem PR nachgezogen wird.
effective_reserve_pctbzw. der Untergrenze des Nutzers; keine von SunCore verursachte Entladung unter die ReserveCheckliste
enunddearchitecture.md; Nutzer-Doku in 4-H)docs/STATUS.mdaktualisiertUNVERIFIEDOffene Fragen an den Maintainer
Für alle Fragen gilt ohne Antwort der jeweils genannte Standard.
fallback_measuredgesetzt wird: Standard: Eine Schritt-für-Schritt-Anleitung kommt mit der Doku in 4-H.Generated by Claude Code